Box Fill Calculator

Does it fit? Count the wires in a box and compare them to its volume.

Box fill inputs

The box

Plastic boxes are stamped; metal boxes list the volume on the label or in the maker's catalog. A ring's marked volume is added to the box.

Wires in the box

Count each wire that enters and ends or splices here, and each one that passes through. Leave out jumpers that start and end inside the box.

Switches and receptacles
Other devices (a different wire size or width)
More: 0 loops · 2 grounds · 1 clamp · 0 fittings
Loops

Spare wire looped through the box, 12 in or longer. Counts twice.

Fittings in the box
Grounds

Rated output

Fits

Volume required

18.00cu in

This wiring needs 18.00 cu in of the 18.00 cu in box. It fits with no room to spare.

RoomRoom for 0 more 12 AWG wires

Box18.00 cu in
Spare room0.00 cu in
Volume295 cm³

Working

  1. 4 × 12 AWG × 2.25 = 9.00
  2. 1 device × 2 × 12 AWG × 2.25 = 4.50
  3. Clamps: 1 × 12 AWG × 2.25 = 2.25
  4. Grounds (2, largest 12 AWG): 1 × 2.25 = 2.25
  5. Total required = 18.00 cu in

Model CB-02

The lamp is green while the counted total is within the box and ring volume, red when it is over. Counts conductors from 14 to 6 AWG in one box. Barrier boxes, isolated grounds and larger wires are not covered; check your code edition and your local inspector (AHJ).

Quick answer

The wiring in this box needs 18.00 cu in. The box and ring give 18.00 cu in, so it fits with no room to spare. Each wire takes room by its size, a switch or receptacle counts as two of its largest wire, and all the grounds together count once.

Rule of thumbTypical rule: 2.00, 2.25 and 2.50 cu in for each 14, 12 and 10 AWG wire; a switch or receptacle counts as two of its wires.

NoteTypical figures. Check your code edition and your local inspector (AHJ). This is an estimate from physics and maker data, not engineering or code advice. Hire a licensed electrician for the work.

How box fill works

Every electrical box has a volume, measured in cubic inches. The wires, devices and fittings inside take up room, and the code (NEC 314.16) limits how much. Too many wires in a box means cramped splices, hot conductors and wire nuts that get pushed back against insulation. The calculator adds up the room the contents need and compares it to the box.

The room each item needs is called its allowance. A wire’s allowance grows with its size: a 14 AWG wire takes 2 cu in, a 12 AWG wire 2.25 cu in and a 10 AWG wire 2.5 cu in. Type the volume of your box, the wire counts and the extras, and the page shows each line of the sum so you can check it by hand.

What gets counted

  • Wires. Count each wire that comes in from outside and ends or splices in the box as one. A wire that passes through uncut counts as one too.
  • Loops. An unbroken loop of spare wire, 12 in or longer, counts as two.
  • Switches and receptacles. Each device counts as two wires of the largest size connected to it. A wide device takes two for every gang it spans.
  • Clamps. If the box has internal cable clamps, add one wire of the largest size in the box. One clamp or four, the count is the same.
  • Luminaire stud and hickey. Each one adds one wire of the largest size, once per type.
  • Grounds. All the grounds together count as one wire of the largest ground size. Past four grounds, each extra adds a quarter of that allowance (2020 and later editions).
  • Not counted. Pigtails that start and end inside the box, locknuts, bushings and other small fittings.

Find the volume of your box

Plastic boxes are stamped with their volume, usually inside the back wall. Metal boxes list it on the label or in the maker’s catalog. If you add a plaster ring, extension ring or raised cover, type its marked volume in the ring box and the calculator adds it to the box.

The page covers boxes up to 100 cu in and wires from 14 to 6 AWG. Bigger boxes and wires larger than 6 AWG follow the pull-box rules in 314.28, which this page does not cover. Barrier boxes are counted one space at a time, and isolated grounds are left out because editions differ on them.

Reading the result

The first tag shows the room the wiring needs, rounded up to the next hundredth of a cubic inch, with a badge for whether it fits. It also shows the same figure in cubic centimetres for boxes sold in metric countries. The second tag shows how much room is left, rounded down, and how many more wires of the largest size would fit. If the box is too full, it shows how far over you are.

The fit check uses the exact total, not the rounded figures. A box whose volume matches the need to the last decimal passes. One that is short by even a hundredth does not.

When the box is too full

You have three ordinary choices. Use a deeper box with more volume, add an extension or plaster ring and type its volume, or reduce the count by moving a splice to another box. Look at the lines: a 2-gang device, a pile of 10 AWG wires or a loop of spare cable often takes more than expected. Changing the largest wire in the box also changes the clamp and fitting counts.

Common mistakes

  • Counting each cable as one wire. A two-conductor cable has two insulated wires, plus a ground that goes into the grounds count.
  • Forgetting the device. A switch or receptacle takes room like two wires.
  • Counting clamps one by one. All internal clamps together count once.
  • Using the wrong volume. The marking on the box is the number to use, plus any ring.
  • Leaving out a ring. A raised cover or extension ring adds its own marked volume.

This is a planning tool. Your code edition and your local inspector (AHJ) decide what is required, and a licensed electrician should do the work.

Worked example

  1. Inputs: 18 cu in box, 4 × 12 AWG, 1 device (12 AWG), internal cable clamps, 2 grounds (largest 12 AWG).
  2. 4 × 12 AWG × 2.25 = 9.00
  3. 1 device × 2 × 12 AWG × 2.25 = 4.50
  4. Clamps: 1 × 12 AWG × 2.25 = 2.25
  5. Grounds (2, largest 12 AWG): 1 × 2.25 = 2.25
  6. Total required = 18.00 cu in

Questions people ask

How many 12 AWG wires fit in a standard single-gang box?

It depends on the box volume, which is marked on the box. For an 18 cu in box with one receptacle, internal clamps and the grounds, the count is 4 wires x 2.25 + 2.25 for the grounds + 2.25 for the clamps + 4.50 for the device = 18.00 cu in. That box holds 4 insulated 12 AWG wires and no more.

What does "2 x for the device" mean?

A switch or receptacle takes room like two wires of the largest size connected to it. A wide device that needs two gangs counts that twice again.

Do ground wires count?

Yes, but all the grounds together count once, sized at the largest ground. In 2020 and later editions, every ground past the fourth adds a quarter of that allowance. Check which edition your area uses.

Do clamps count?

Internal cable clamps take one allowance of the largest wire in the box, however many clamps there are. Clamps outside the box take none.

Do wire nuts or locknuts count?

No. Small fittings such as locknuts and bushings take no allowance, and neither does a short pigtail that starts and ends inside the box.

Where do I find my box volume?

Plastic boxes are stamped with it; metal boxes list it on the label or in the maker's catalog. Add any ring or extension, and type each in cubic inches.

Sources

Data last verified: Page updated

Written and checked by Ali, who is not a licensed electrician.

Before you wire anything

These calculators give estimates worked out from physics and published maker data. They are not engineering, design or code advice, and they do not replace an inspection.

Electrical codes differ by edition and by town. Your local inspector, the authority having jurisdiction (AHJ), has the final say on wire size, conduit, boxes and breakers.

Mains wiring can kill and can start fires. Unless you are trained for it, hire a licensed electrician, and get a permit where your town requires one.