Wire Size Calculator
The wire gauge for your load and your run: the smallest AWG size for copper or aluminum.
Sets the load to the breaker size. For a load that runs 3 hours or more, enter its amps instead.
NM-B is the sheathed cable used in most houses; wires in conduit means single THHN/THWN-2 wires.
Rated output
Sized to fitUse at least
4AWG
Use at least: 4 AWG copper (21.15 mm²).
Because: distance sets this size; current alone needs 6 AWG (60 °C rating 55 A typical).
- Rating column: 60 °C, because NM-B cable is limited to its 60 °C rating.
- 4 or more current-carrying wires in one conduit, hot attics (above 86 °F) and bundled cables lower the rating.
- Some installs may use a smaller size under code exceptions; we size so the wire's typical rating is at least the load.
Working
- Current: 50 A
- Current alone: 6 AWG copper, 60 °C rating 55 A typical (the first size rated at least 50 A)
- Drop with 6 AWG = 2 × 160 ft × 50 A × 0.4901 Ω ÷ 1,000 = 7.84 V (3.27%), over 3%
- Drop with 4 AWG = 2 × 160 ft × 50 A × 0.3082 Ω ÷ 1,000 = 4.93 V (2.05%), within 3%
- Answer: the larger of the two, 4 AWG copper
Model WV-01
Typical figures from physics and maker data, one rating per input. The lamp lights only when no size can be given. Check your code edition and your local inspector (AHJ).
Quick answer
For a 50 A load at 240 V over 160 ft of copper NM-B cable, use at least 4 AWG copper (21.15 mm²): current alone needs 6 AWG (60 °C rating 55 A typical), and the distance needs the larger wire to keep the drop at 2.05%.
Rule of thumbTypical: 50 A on copper takes 6 AWG at 60 °C (8 AWG only with 75 °C terminals); long runs need bigger wire.
NoteTypical figures. Check your code edition and your local inspector (AHJ). This is an estimate from physics and maker data, not engineering or code advice. Hire a licensed electrician for the work.
| Wire size, AWG | ||||||
|---|---|---|---|---|---|---|
| Load | 10 AWG | 8 AWG | 6 AWG | 4 AWG | 3 AWG | 2 AWG |
| 30 A | 96 | 153 | 244 | 389 | 490 | 619 |
| 40 A | - | 115 | 183 | 292 | 368 | 464 |
| 50 A | - | - | 146 | 233 | 294 | 371 |
| 60 A | - | - | - | 194 | 245 | 309 |
The longest one-way run, in feet, before the drop on a 240 V single phase circuit reaches 3% (stranded copper). A dash means that size is too small for the current.
AWG wire gauge chart: diameter in inches and mm, area in mm²
4 AWG wire is 5.19 mm (0.2043 in) across with 21.15 mm² of copper, the size the example above calls for, and every lower gauge number is 12.3% wider.
AWG to mm² converter
12 AWG is 2.05 mm (0.0808 in) across, 3.31 mm². Metric sizes either side: 2.5 mm² (24% less area) and 4 mm² (21% more). Copper, solid, 20 °C: 1.59 Ω per 1,000 ft (5.21 Ω per km); aluminum 2.60 Ω (8.54 Ω per km).
| AWG | Inches across | mm across | mm² area | Ω/1,000 ft copper |
|---|---|---|---|---|
| 4/0 | 0.4600 | 11.68 | 107.22 | 0.0490 |
| 3/0 | 0.4096 | 10.40 | 85.03 | 0.0618 |
| 2/0 | 0.3648 | 9.27 | 67.43 | 0.0779 |
| 1/0 | 0.3249 | 8.25 | 53.48 | 0.0983 |
| 1 | 0.2893 | 7.35 | 42.41 | 0.124 |
| 2 | 0.2576 | 6.54 | 33.63 | 0.156 |
| 3 | 0.2294 | 5.83 | 26.67 | 0.197 |
| 4 | 0.2043 | 5.19 | 21.15 | 0.248 |
| 5 | 0.1819 | 4.62 | 16.77 | 0.313 |
| 6 | 0.1620 | 4.12 | 13.30 | 0.395 |
| 7 | 0.1443 | 3.66 | 10.55 | 0.498 |
| 8 | 0.1285 | 3.26 | 8.37 | 0.628 |
| 9 | 0.1144 | 2.91 | 6.63 | 0.792 |
| 10 | 0.1019 | 2.59 | 5.26 | 0.999 |
| 11 | 0.0907 | 2.30 | 4.17 | 1.26 |
| 12 | 0.0808 | 2.05 | 3.31 | 1.59 |
| 13 | 0.0720 | 1.83 | 2.62 | 2.00 |
| 14 | 0.0641 | 1.63 | 2.08 | 2.53 |
| 15 | 0.0571 | 1.45 | 1.65 | 3.18 |
| 16 | 0.0508 | 1.29 | 1.31 | 4.02 |
| 17 | 0.0453 | 1.15 | 1.04 | 5.06 |
| 18 | 0.0403 | 1.02 | 0.823 | 6.38 |
| 19 | 0.0359 | 0.912 | 0.653 | 8.05 |
| 20 | 0.0320 | 0.812 | 0.518 | 10.2 |
| 21 | 0.0285 | 0.723 | 0.410 | 12.8 |
| 22 | 0.0253 | 0.644 | 0.326 | 16.1 |
| 23 | 0.0226 | 0.573 | 0.258 | 20.4 |
| 24 | 0.0201 | 0.511 | 0.205 | 25.7 |
This chart gives size only. How many amps a wire may carry depends on its insulation temperature rating, how it is installed and the electrical code: the wire size calculator above works that out for your load and run.
Fine wire: 25 to 40 AWG
| AWG | Inches across | mm across | mm² area | Ω/1,000 ft copper |
|---|---|---|---|---|
| 25 | 0.0179 | 0.455 | 0.162 | 32.4 |
| 26 | 0.0159 | 0.405 | 0.129 | 40.8 |
| 27 | 0.0142 | 0.361 | 0.102 | 51.5 |
| 28 | 0.0126 | 0.321 | 0.0810 | 64.9 |
| 29 | 0.0113 | 0.286 | 0.0642 | 81.8 |
| 30 | 0.0100 | 0.255 | 0.0509 | 103 |
| 31 | 0.00893 | 0.227 | 0.0404 | 130 |
| 32 | 0.00795 | 0.202 | 0.0320 | 164 |
| 33 | 0.00708 | 0.180 | 0.0254 | 207 |
| 34 | 0.00630 | 0.160 | 0.0201 | 261 |
| 35 | 0.00561 | 0.143 | 0.0160 | 329 |
| 36 | 0.00500 | 0.127 | 0.0127 | 415 |
| 37 | 0.00445 | 0.113 | 0.0100 | 523 |
| 38 | 0.00397 | 0.101 | 0.00797 | 660 |
| 39 | 0.00353 | 0.0897 | 0.00632 | 832 |
| 40 | 0.00314 | 0.0799 | 0.00501 | 1,049 |
Calculated from the AWG law. Printed tables that round the diameter first differ by up to about 3% for the finest sizes.
Sizes are for solid wire. A stranded wire of the same gauge has the same copper area, is a little thicker overall, and its resistance is up to about 2% higher.
AWG and metric sizes are two separate series, so no AWG size equals a metric one: 2.5 mm² sits between 14 AWG (2.08 mm²) and 13 AWG (2.62 mm²). The converter names the metric sizes on either side. A metric cable is not a drop-in swap for an AWG one: check its own rating.
How the calculator picks a size
Picking a wire gauge means passing two tests. It must carry the current without getting too hot, and over the length of the run it must not lose too much voltage. Each test gives a smallest size, and the answer is the larger of the two.
- Current. The calculator takes the load in amps, or the breaker size if you pick one, and finds the first wire whose typical current rating from the makers’ charts is at least that much. Small copper wire has a fixed limit whatever the chart says: 15 A for 14 AWG, 20 A for 12 AWG and 30 A for 10 AWG. Wiring a switch with that wire? See the switch wiring diagram.
- Distance. It then finds the smallest wire that keeps the voltage drop within your limit at the real load, with the wire at 75 °C. The method is the same as on the voltage drop calculator.
On a short run the current decides. On a long run the distance usually does, and the result tells you which one set the size.
60 °C or 75 °C: which rating applies
The calculator uses the 60 °C rating unless you choose wires in conduit and tick that both ends are marked 75 °C. Wire carries more current when it is allowed to run hotter, so the makers’ charts list a rating for each temperature. The rating you can use is limited by the coolest part of the circuit, which is usually where the wire connects. Breakers and equipment for circuits of 100 A or less are treated as 60 °C parts unless they are marked 75 °C (NEC 110.14(C)(1)). Single wires in conduit are usually THHN/THWN-2, the nylon-coated building wire sold for conduit. NM-B cable, the plastic-sheathed cable used in most houses, is limited to its 60 °C rating in any case (NEC 334.80).
That is why the usual answer for 50 A is 6 AWG copper, and 8 AWG copper only with 75 °C terminals at both ends.
Loads that run for hours
A load that runs 3 hours or more, such as an EV charger, is counted at 125% when choosing the wire (NEC 210.19(A)(1)). Tick “runs 3 hours or more” and the calculator multiplies the load by 1.25 for the current test. The voltage drop still uses the real current, because that is what flows in the wire. If you pick a breaker size instead, it is used as it is.
When the typical rating is too high
The typical rating is too high in hot attics, with four or more current-carrying wires in one conduit, and for cables bundled tightly together. The charts assume surroundings at 86 °F and no more than three current-carrying wires together, and those cases all lower what a wire can carry. The calculator does not apply those corrections, so in those places choose a larger wire or ask an electrician.
Why a lower gauge number is a thicker wire
Every lower gauge number makes the wire 12.3% wider, so 6 steps double the diameter and 3 steps double the area: 4 AWG has about four times the area of 10 AWG. The American Wire Gauge fixes two sizes, 0000 (4/0) at 0.4600 in and 36 at 0.0050 in, and spaces 39 even steps between them (NBS Handbook 100): diameter = 0.005 in × 92^((36 − n) ÷ 39), with 1/0 to 4/0 counted as 0 to −3. Thicker wire is named in kcmil, thousands of circular mils: 250 kcmil is 126.68 mm².
What the wire size result does not cover
It stops at 100 A: feeders and services need more checks than one current rating, so it asks you to call an electrician. It does not pick a breaker, size the ground wire, or offer aluminum smaller than 8 AWG. Some installations may use a smaller wire under exceptions in the code; this tool always picks a wire whose typical rating is at least the load, which errs on the large side.
Worked example
- Inputs: 50 A load, 160 ft one way, copper NM-B cable, single phase 240 V, 3% drop limit.
- Current: 50 A
- Current alone: 6 AWG copper, 60 °C rating 55 A typical (the first size rated at least 50 A)
- Drop with 6 AWG = 2 × 160 ft × 50 A × 0.4901 Ω ÷ 1,000 = 7.84 V (3.27%), over 3%
- Drop with 4 AWG = 2 × 160 ft × 50 A × 0.3082 Ω ÷ 1,000 = 4.93 V (2.05%), within 3%
- Answer: the larger of the two, 4 AWG copper
Questions people ask
What size wire for a 50 amp circuit?
6 AWG copper for NM-B cable or unmarked terminals; 8 AWG copper only where the wires run in conduit and both ends are marked 75 °C. Those are the typical ratings at 60 °C (55 A) and at 75 °C (50 A). Distance can push it larger: at 240 V, 6 AWG copper reaches a 3% drop at about 146 ft, so a 160 ft run needs 4 AWG.
What size wire for a 30 amp circuit?
10 AWG copper. Its typical rating is 30 A at 60 °C, which is also the fixed limit for small copper wire, so it suits NM-B cable and unmarked terminals. A long run can need a bigger wire; enter your length above to see.
Does distance change the wire size?
Yes. The current sets the smallest wire that stays cool enough, and the distance sets the smallest wire that keeps the voltage drop in check. The calculator works out both and gives the larger. A long run often needs a wire one or two sizes bigger than the current alone calls for. A bigger wire than the minimum is fine: it runs cooler and loses less voltage, but check that it fits the terminals. The breaker still depends on the load, not on the wire.
Is 12 gauge wire thicker than 14 gauge?
Yes: 12 gauge is 2.05 mm (0.0808 in) across with 3.31 mm² of copper, and 14 gauge is 1.63 mm (0.0641 in) with 2.08 mm². A lower AWG number is always a thicker wire; the chart above lists every size from 4/0 to 40.
Copper or aluminum?
Aluminum carries less current for its size and drops about 1.64 times as much voltage as copper of the same size, so it needs a bigger wire: at 50 A on the 60 °C rating, 4 AWG aluminum against 6 AWG copper. The calculator offers aluminum from 8 AWG up. Check that the breaker and the equipment terminals accept aluminum wire.
How do you measure wire gauge?
Measure the bare metal conductor with calipers or a micrometer, then read the diameter off the chart above. Gauge is based on the size of the conductor itself, not the total diameter of the insulated wire. A wire gauge tool does the same with slots: the wire that fits the slot for its gauge number is that gauge.
Related guides
Sources
- IAEI Magazine: NEC rules about wire temperature ratings and terminationsiaeimagazine.org
- Eaton: Application of 100%-rated molded case circuit breakers (AP01200008E)eaton.com
- IAEI Magazine: 100% vs 80%: Choosing the right OCPD solutioniaeimagazine.org
- Cerrowire: Ampacity Chartscerrowire.com
- Southwire: Romex SIMpull NM-B, SPEC 10028southwire.com
- Southwire: SIMpull THHN/THWN-2, SPEC 22060southwire.com
- Southwire: SER aluminum, SPEC 10041southwire.com
- Encore Wire: Wire Ampacity Size Tableencorewire.com
- ExpertCE: How to Calculate Wire Gauge for a 50 Amp Circuitexpertce.com
- IAEI Magazine: Voltage Drop Formulasiaeimagazine.org
- SlashGear: What Is The 80% Rule For Circuit Breakers?slashgear.com
- NBS Handbook 100, Copper Wire Tables (NIST)nist.gov
- NBS Handbook 109, Aluminum Wire Tables (NIST)nist.gov
- Aluminum Association, Table 16.3aluminum.org
- Lapp Tannehill: Metric to AWG conversion chartlapptannehill.com
- MyCableEngineering: Metric to AWG conversionmycableengineering.com
- MyCableEngineering: Conductor resistance (IEC 60228)mycableengineering.com
- August Electronics: How wire gauge is measuredaeicm.com
- Wikipedia: American wire gaugewikipedia.org
Built and checked by Ali, who is not a licensed electrician.
Link to this calculator: https://wattplate.com/wire-size-calculator/
Before you wire anything
These calculators give estimates worked out from physics and published maker data. They are not engineering, design or code advice, and they do not replace an inspection.
Electrical codes differ by edition and by town. Your local inspector, the authority having jurisdiction (AHJ), has the final say on wire size, conduit, boxes and breakers.
Mains wiring can kill and can start fires. Unless you are trained for it, hire a licensed electrician, and get a permit where your town requires one.