Duct Size Calculator

Round or rectangular duct size from airflow and a friction rate or velocity.

Size by

Inches of water per 100 ft of duct; 0.10 is the common default.

Duct
Shape
Units
Work out my friction rate

Fill both boxes to work out a rate.

HVAC School: friction rate = available static pressure × 100 ÷ total effective length. Filling both sets the friction rate above.

Rated output

Within 900 fpm

Round duct, exact solve

9.7in

400 CFM at 0.10 in. w.c. per 100 ft needs a 9.7 in round duct; the next whole inch, 10 in, moves it at 733 fpm.

Rule-of-thumb estimate for one duct section in standard air (sea level, about 70 °F). A Manual J load calculation and a duct design by a pro size the real system.

Next whole inch10 in
Velocity733 fpm
Friction, per 100 ft0.085 in. w.c.
Airflow400 CFM
Friction rate0.10 in. w.c.
Supply limit900 fpm

Working

  1. Airflow = 400 CFM
  2. Friction rate = 0.10 in. w.c. per 100 ft
  3. Exact size: the round duct whose Darcy-Colebrook friction = 0.10 at 400 CFM is 9.684 in (782 fpm there), rounded up to 9.7 in
  4. Velocity at 10 in = 400 CFM ÷ (π × (10 ÷ 24)²) = 400 ÷ 0.5454 sq ft = 733 fpm
  5. Friction at 10 in = (1,200 × 0.0213 ÷ 10) × 0.075 × (733.4 ÷ 1,097)² = 0.085 in. w.c. per 100 ft (Re 62,778)
  6. Next whole inch: 10 in · 733 fpm · 0.085 in. w.c. per 100 ft

Model HC-03

Velocity limit 900 fpm supply, 700 return (Manual D, per Energy Vanguard). Friction from Darcy-Weisbach and Colebrook for galvanized steel.

  • Matching area alone is wrong: an 8 × 8 in duct equals 8.7 in round (Huebscher).
  • ASHRAE: fully stretched flex has about 50% more resistance than metal; Energy Vanguard: flex pulled tight can use the same size. Sag and compression cut airflow a lot.

Quick answer

400 CFM at 0.10 in. w.c. per 100 ft needs a 9.7 in round duct (the exact solve, rounded up); the next whole inch, 10 in, moves it at 733 fpm. With one side of 8 in, an equal-friction rectangle is 8 × 10 in.

Rule of thumbTypical: 400 CFM at 0.10 in. w.c. per 100 ft needs a 9.7 in round duct; the next whole inch, 10 in, moves it at 733 fpm.

NoteRule-of-thumb estimate for one duct section in standard air. A Manual J load calculation and a duct design by a pro size the real system. This is an estimate from physics and maker data, not engineering or code advice. Hire a licensed HVAC contractor for the work.

Round duct by airflow: exact size in inches at 0.08 and 0.10 in. w.c. per 100 ft, then the next whole inch at 0.10 and its velocity
CFMExact, 0.08Exact, 0.10Next inchfpm there
504.74.55367
1006.15.86509
2007.97.58573
40010.29.710733
80013.212.613868
1,20015.414.715978 over the 900 fpm supply limit

Galvanized round duct, standard air. * Over the 900 fpm supply limit (Manual D, per Energy Vanguard): go up a size.

How the calculator sizes a duct

Type the airflow in CFM and either a friction rate or a velocity. A friction rate is the pressure the duct may use up for every 100 ft of its length, in inches of water column (in. w.c.). The calculator then finds the round duct that carries your airflow at exactly that rate.

It does this with physics, not with a chart. The duct friction chart in the ASHRAE Handbook is a plot of two equations: Darcy-Weisbach for the pressure loss and Colebrook for the friction factor, drawn for galvanized steel duct (roughness 0.0003 ft) and standard air (0.075 lb per cubic foot, about 70 °F at sea level). This page solves the same equations for your numbers:

  • Velocity: CFM ÷ area, where the area of a round duct is π × (D ÷ 24)² sq ft with D in inches.
  • Reynolds number: 8.56 × D × velocity, for standard air.
  • Friction per 100 ft: (1,200 × f ÷ D) × 0.075 × (velocity ÷ 1,097)², with the friction factor f found from Colebrook’s equation by repeating it until it stops changing.

The calculator tries diameters until the friction matches your rate. In velocity mode it skips that search: the area is the airflow divided by the velocity you chose.

Why the answer is rounded up

The exact solve is rarely a size you can buy, so the page rounds it up to the next 0.1 in, then names the next whole inch and works out the velocity and friction at that size. A bigger duct always has less friction than your rate, so the size you see never asks the fan for more than you allowed.

For the default job, 400 CFM at 0.10 in. w.c. per 100 ft, the exact size is 9.684 in. The page shows 9.7 in, and the next whole inch, 10 in, moves the air at 733 fpm with 0.085 in. w.c. of friction per 100 ft.

Friction rate or velocity?

Most people size supply ducts by friction rate. The 0.10 default is the figure ACCA says people use everywhere because it sits in the middle of the chart, and ASHRAE puts low-pressure systems between 0.05 and 0.20. A better rate comes from your own system: available static pressure × 100 ÷ total effective length (HVAC School). Open Work out my friction rate, type both figures, and the rate fills the box, rounded down so the duct comes out a little bigger, never smaller. Energy Vanguard’s worked design lands on 0.073 this way.

Size by velocity when you want to hold a speed instead, such as a return you want quiet. Type the velocity and the page sizes the duct straight from the area.

Supply and return limits

Manual D lists 900 fpm as the highest velocity for a home’s supply ducts and 700 fpm for returns (per Energy Vanguard). Pick Supply or Return and the pilot lamp compares the velocity at the size on the plate with that limit: green at or below it, red above it, with a size that fits. The same 400 CFM that runs at 733 fpm in a 10 in duct is fine as a supply but too fast for a return, which needs 11 in.

To check a duct you already have, type its size in Check a size. The plate then shows the velocity and friction at that size, and the lamp reads it.

Rectangular ducts

A rectangle with the same area as a round duct has more friction, because more of its air rubs on the walls. The Huebscher equation gives the round size with the same airflow and friction: De = 1.30 × (a × b)^0.625 ÷ (a + b)^0.25. Choose Rect, type one side, and the calculator solves for the other side so the rectangle’s equivalent round is at least the exact size, rounded up to the next 0.5 in (10 mm).

With an 8 in side, the default job needs an 8 × 10 in rectangle: its equivalent round is 9.762 in, the air moves at 720 fpm through the real 80 sq in of area, and the friction is 0.096 in. w.c. per 100 ft. That is why matching area alone is wrong.

Metric units

The Units band switches every box to litres per second, pascals per metre, metres per second and millimetres. The page still works in US units inside and converts with NIST factors: 1 CFM is 0.4719474 L/s and 1 in. w.c. per 100 ft is 8.1722 Pa/m. The exact size shows in millimetres, rounded up to the next 1 mm, and the next whole inch keeps its inch size with millimetres beside it.

What this does not cover

This sizes one straight section of galvanized duct in standard air. It leaves out fittings and their equivalent lengths, the blower’s pressure budget, altitude and temperature corrections, flex duct sag and compression, flat oval duct and grille sizing. A Manual J load calculation sets the airflow each room needs, and a duct design by a pro sizes the real system.

Worked example

  1. Inputs: 400 CFM supply duct, friction rate 0.10 in. w.c. per 100 ft, round, US units.
  2. Airflow = 400 CFM
  3. Friction rate = 0.10 in. w.c. per 100 ft
  4. Exact size: the round duct whose Darcy-Colebrook friction = 0.10 at 400 CFM is 9.684 in (782 fpm there), rounded up to 9.7 in
  5. Velocity at 10 in = 400 CFM ÷ (π × (10 ÷ 24)²) = 400 ÷ 0.5454 sq ft = 733 fpm
  6. Friction at 10 in = (1,200 × 0.0213 ÷ 10) × 0.075 × (733.4 ÷ 1,097)² = 0.085 in. w.c. per 100 ft (Re 62,778)
  7. Next whole inch: 10 in · 733 fpm · 0.085 in. w.c. per 100 ft
  8. The same duct as a rectangle with one 8 in side:
  9. Other side: 1.30 × (8 × b)^0.625 ÷ (8 + b)^0.25 = 9.684 in at b = 9.836 in, rounded up to 10 in
  10. Equivalent round of 8 × 10 in = 1.30 × (8 × 10)^0.625 ÷ (8 + 10)^0.25 = 9.762 in
  11. Velocity in 8 × 10 in = 400 CFM ÷ (8 × 10 ÷ 144) = 400 ÷ 0.5556 sq ft = 720 fpm
  12. Friction at the 9.762 in equivalent = 0.096 in. w.c. per 100 ft
  13. 8 × 10 in rectangle · equivalent round 9.8 in · 720 fpm · 0.096 in. w.c. per 100 ft

Questions people ask

What friction rate should I use?

Many residential designs use about 0.08 to 0.10 in. w.c. per 100 ft, and 0.10 is the figure most people reach for because it sits in the middle of the chart in the Manual D book (ACCA). A design rate comes from your own system: available static pressure × 100 ÷ total effective length, so 0.10 × 100 ÷ 200 ft = 0.05 (HVAC School). A blanket 0.10 tends to undersize.

What size duct do I need for 400 CFM?

At 0.10 in. w.c. per 100 ft the exact round size is 9.7 in, so 10 in, which moves 400 CFM at about 733 fpm. A return held to 700 fpm needs 10.3 in, so 11 in, at 606 fpm.

What is the maximum duct velocity?

Manual D lists 900 fpm for supply ducts and 700 fpm for returns (per Energy Vanguard). Faster air is louder. The pilot lamp on the result turns red above the limit for the duct you picked.

How do I convert a rectangular duct to round?

Use the Huebscher equation: De = 1.30 × (a × b)^0.625 ÷ (a + b)^0.25. A 10 × 16 in duct is 13.7 in round (aircondlounge) and 300 × 500 mm is 420 mm (Engineering ToolBox). Matching area alone is wrong: an 8 × 8 in duct is 8.7 in round.

Does flex duct need a bigger size?

ASHRAE: fully stretched flex has about 50% more resistance than metal; Energy Vanguard: flex pulled tight can use the same size. Sag and compression cut airflow a lot.

Can I size a whole system with this?

No. It sizes one duct section in standard air. A real system needs a Manual J load calculation and a duct design by a pro, who counts every run, the fittings and the static pressure the blower has to spare.

Sources

Data last verified: Page updated

Written and checked by Ali, who is not a licensed electrician.

Before you wire anything

These calculators give estimates worked out from physics and published maker data. They are not engineering, design or code advice, and they do not replace an inspection.

Electrical codes differ by edition and by town. Your local inspector, the authority having jurisdiction (AHJ), has the final say on wire size, conduit, boxes and breakers.

Mains wiring can kill and can start fires. Unless you are trained for it, hire a licensed electrician, and get a permit where your town requires one.