BTU Calculator for a Room Air Conditioner
The BTU/h one room needs, from the ENERGY STAR room table.
Shaded −10%, very sunny +10% on the table figure (ENERGY STAR).
+600 BTU/h each past 2.
Optional: the size on its label.
The furnace's input rating, not its output.
80%: mid-efficiency, DOE. The furnace label or manual gives yours.
Space heaters, baseboards and electric furnaces: the watts on the label.
Optional: from a load calculation by a pro.
Rated output
No readingCooling estimate
7,200BTU/h
0.60 ton · 2.11 kW. Pick a room unit of at least 7,200 BTU/h; the next ENERGY STAR size is 8,000 BTU/h.
CheckLast good result. Check the field above.
Unit check
- Rule-of-thumb estimate (ENERGY STAR room method). A Manual J load calculation by a pro sizes central systems and whole homes.
- Bigger is not better: an oversized unit cools before it dries the air and the room feels damp and clammy (ENERGY STAR).
Working
- Floor area = 20 ft × 10 ft = 200 sq ft
- 200 sq ft: 6,000 BTU/h (ENERGY STAR, 150 up to 250 sq ft)
- Very sunny: + 10% = 6,600
- 3 people: + 600 = 7,200
- Tons = BTU/h ÷ 12,000 = 7,200 ÷ 12,000 = 0.60 ton
- kW = BTU/h × 3,516.853 ÷ 12,000,000 = 7,200 × 3,516.853 ÷ 12,000,000 = 2.11 kW
Model HC-01
Room sizes from ENERGY STAR. Lamp, with your unit typed: green from the estimate up to the next ENERGY STAR size, amber above it (oversized), red below the estimate.
Quick answer
A 200 sq ft room that is very sunny, with 3 people, needs about 7,200 BTU/h of cooling (0.60 ton, 2.11 kW). The ENERGY STAR table gives 6,000 BTU/h for its size before the sun and people adjustments, and the next ENERGY STAR size is 8,000 BTU/h.
Rule of thumbTypical: a 200 sq ft room needs 6,000 BTU/h (ENERGY STAR); very sunny adds 10% and each person past two adds 600, so 7,200 BTU/h.
NoteRule-of-thumb estimate from the ENERGY STAR room method; furnace output is about input × AFUE. A Manual J load calculation by a pro sizes the real system. This is an estimate from physics and maker data, not engineering or code advice. Hire a licensed HVAC contractor for the work.
| Area, sq ftArea, m² | BTU/h | Tons | kW |
|---|---|---|---|
| 100 up to 1509.3 up to 13.9 | 5,000 | 0.42 | 1.47 |
| 150 up to 25013.9 up to 23.2 | 6,000 | 0.50 | 1.76 |
| 250 up to 30023.2 up to 27.9 | 7,000 | 0.58 | 2.05 |
| 300 up to 35027.9 up to 32.5 | 8,000 | 0.67 | 2.34 |
| 350 up to 40032.5 up to 37.2 | 9,000 | 0.75 | 2.64 |
| 400 up to 45037.2 up to 41.8 | 10,000 | 0.83 | 2.93 |
| 450 up to 55041.8 up to 51.1 | 12,000 | 1.00 | 3.52 |
| 550 up to 70051.1 up to 65 | 14,000 | 1.17 | 4.10 |
| 700 up to 1,00065 up to 92.9 | 18,000 | 1.50 | 5.28 |
| 1,000 up to 1,20092.9 up to 111.5 | 21,000 | 1.75 | 6.15 |
| 1,200 up to 1,400111.5 up to 130.1 | 23,000 | 1.92 | 6.74 |
| 1,400 up to 1,500130.1 up to 139.4 | 24,000 | 2.00 | 7.03 |
| 1,500 up to 2,000139.4 up to 185.8 | 30,000 | 2.50 | 8.79 |
| 2,000 up to 2,500185.8 up to 232.3 | 34,000 | 2.83 | 9.96 |
Each band runs from its first figure up to the next, for an 8 ft ceiling (ENERGY STAR). Before the sun, people and kitchen adjustments.
| Input | 80% | 90% | 95% | 97% |
|---|---|---|---|---|
| 40,000 | 32,000 | 36,000 | 38,000 | 38,800 |
| 60,000 | 48,000 | 54,000 | 57,000 | 58,200 |
| 80,000 | 64,000 | 72,000 | 76,000 | 77,600 |
| 100,000 | 80,000 | 90,000 | 95,000 | 97,000 |
| 120,000 | 96,000 | 108,000 | 114,000 | 116,400 |
Output is about input × AFUE; the label wins.
How the calculator sizes a room
The calculator follows the ENERGY STAR method for room air conditioners: the window, wall and portable units that cool one room. It works in four steps, and the working on the plate shows each step with your numbers.
- Floor area. Length times width, or type the area. Metric sizes are turned into square feet first, because the table is in square feet.
- The table. ENERGY STAR lists the capacity a room needs by its floor area, from 5,000 BTU/h for 100 up to 150 sq ft to 34,000 BTU/h for 2,000 up to 2,500 sq ft. Each band starts at its first figure, so a room of exactly 150 sq ft takes the 6,000 BTU/h row. The capacities assume an 8 ft ceiling.
- Sun. A heavily shaded room takes 10% off the table figure. A very sunny room adds 10%.
- People and kitchen. Add 600 BTU/h for each person past two who regularly uses the room, and 4,000 BTU/h if the unit cools a kitchen.
The percentage applies to the table figure only. The 600 and the 4,000 are fixed amounts, so they come after the sun adjustment and are never scaled by it.
The answer is rounded up to the next 100 BTU/h. Room units come in steps, so the plate also names the next ENERGY STAR size at or above your estimate: that is the size to look for on the label.
Tons, BTU/h and kilowatts
Air conditioners are rated in BTU per hour (BTU/h), the heat they move out of the room each hour. A ton of cooling is 12,000 BTU/h (NIST, Trane), so a 24,000 BTU/h unit is a 2 ton unit. In watts, one ton is about 3.517 kW (NIST), which makes 1 kW about 3,412 BTU/h, the figure the EIA uses.
The kilowatts on the plate are cooling power: the heat the unit removes. They are not the electricity it draws from the wall. That figure is on the unit’s label in watts or amps, and the watts to amps calculator turns one into the other.
Why bigger is not better
It is tempting to go a size or two up for hot days. ENERGY STAR and Natural Resources Canada both warn against it: a unit that is too large cools the room before it has a chance to remove the humidity, and the room feels damp and clammy.
Type the size of a unit you own or are looking at, and the pilot lamp on the plate checks it against the estimate.
Higher ceilings
The ENERGY STAR capacities are calculated for an 8 ft ceiling. With higher ceilings, ENERGY STAR says you may want a unit with more capacity, but it gives no figure for how much, and other guides disagree with each other. So the calculator adds no percentage. Tick the ceiling box and the plate shows the note while the estimate stays the same.
One room, not a whole house
The ENERGY STAR table stops at 2,500 sq ft, and so does the calculator. Central air conditioners and heat pumps that serve a whole home are sized from a load calculation: a pro looks at the walls, windows, insulation, air leaks and the local climate, which a rule per square foot cannot see. ACCA’s Manual J is the usual method for that work.
An estimate above 34,000 BTU/h, the largest size in the ENERGY STAR list, points the same way: several room units or a central system, and a pro to size them.
Heating: furnace output and electric heat
Switch the plate to Heating. A furnace label lists its input, the fuel it burns, and its output, the heat it delivers: about input × AFUE, so 100,000 BTU/h at 80% gives 80,000. Type the heat a load calculation calls for and the plate shows the input to look for. Electric heaters turn every watt into heat (DOE): 1,500 W gives 5,118 BTU/h. A heat pump gives less heat as it gets colder, so a pro sizes it from the maker’s capacity at your design temperature; running costs are on the heat pump calculator.
Common mistakes
- Using one rate per square foot. The table needs 30 BTU/h per sq ft at 200 sq ft but only about 17 at 1,750 sq ft. A flat rate undersizes small rooms or oversizes large ones.
- Reading kW as running cost. Cooling kilowatts are heat moved, not power drawn. Use the label’s watts for running cost.
Worked example
- Inputs: a 20 ft × 10 ft room (200 sq ft), very sunny, 3 people, not a kitchen.
- Floor area = 20 ft × 10 ft = 200 sq ft
- 200 sq ft: 6,000 BTU/h (ENERGY STAR, 150 up to 250 sq ft)
- Very sunny: + 10% = 6,600
- 3 people: + 600 = 7,200
- Tons = BTU/h ÷ 12,000 = 7,200 ÷ 12,000 = 0.60 ton
- kW = BTU/h × 3,516.853 ÷ 12,000,000 = 7,200 × 3,516.853 ÷ 12,000,000 = 2.11 kW
Questions people ask
What size air conditioner do I need for a 300 sq ft room?
ENERGY STAR lists 7,000 BTU/h for 250 up to 300 sq ft and 8,000 BTU/h for 300 up to 350 sq ft, for an 8 ft ceiling, so a room of exactly 300 sq ft starts at 8,000. Add 10% if the room is very sunny and take off 10% if it is heavily shaded.
How many BTU per square foot?
There is no single figure. The ENERGY STAR table works out to 30 BTU/h per sq ft for a 200 sq ft room (6,000 BTU/h), 24 at 500 sq ft (12,000) and about 17 at 1,750 sq ft (30,000): bigger rooms need less for each square foot. Use the table rather than a flat rate.
How many BTU do I need to heat my house?
No flat rate per square foot works; DOE warns against sizing from floor area. In DOE's example, one 2,000 sq ft Raleigh house needs 46,100 BTU/h as built and 21,300 after insulation, window and air-sealing upgrades, so the same rule cannot fit both. A Manual J load calculation by a pro sizes the real system.
Is a furnace's BTU rating input or output?
The label lists both: input is the fuel it burns, output the heat it delivers, about input × AFUE. Goodman lists its 100,000 BTU/h, 80% AFUE furnace at 80,000 output. Size on output, and do not copy the old furnace: GBA finds most put out 2 to 4 times the heat the house needs.
What happens if the AC is too big?
It cools the room before it has a chance to remove the moisture, so the room feels damp and clammy (ENERGY STAR, NRCan). Bigger is not better: look for the next ENERGY STAR size at or above the estimate.
Does the old 500 sq ft per ton rule work for a whole house?
Trane's chart pairs 2,000 sq ft with 4 tons and a Florida contractor survey averaged 502 sq ft per ton (FSEC), but load calculations on newer, tighter homes usually come in far lower, so the old rule often oversizes (Energy Vanguard; ENERGY STAR on oversizing). A Manual J load calculation by a pro decides.
Sources
- ENERGY STAR: Room Air Conditioners, buying guidance (capacity by room size, adjustments)energystar.gov
- Natural Resources Canada: Guide to room air conditionerscanada.ca
- Frigidaire: Room Air Conditioner Size Guidefrigidaire.com
- NIST SP 811, Appendix B.8: conversion factors (ton of refrigeration)nist.gov
- Trane: What does ton mean in HVAC?trane.com
- EIA: British thermal units (Btu)eia.gov
- Florida Solar Energy Center: FSEC-PF-289-95 (square feet per ton survey)ucf.edu
- Energy Vanguard: Air Conditioner Sizing, Load Calculations vs Rules of Thumbenergyvanguard.com
- DOE Building America: Right-Size Heating and Cooling Equipment (fact sheet 31318)energy.gov
- Goodman SS-GM9S80 / GC9S80 spec sheet, 80% AFUE furnaces (input and output BTU/h)shopify.com
- Green Building Advisor: Replacing a Furnace or Boilergreenbuildingadvisor.com
- Energy Vanguard: It's Hard to Undersize a Heating Systemenergyvanguard.com
- DOE: Home Heating Systems guide (AFUE definition; mid-efficiency 80-83%, high-efficiency 90-98.5%)energy.gov
- ENERGY STAR furnaces key product criteria (95% AFUE South, 97% North)energystar.gov
- DOE Energy Saver: Electric resistance heating (all incoming electric energy is converted to heat)energy.gov
- ENERGY STAR Heat Pump Specification Version 6.2 (cold weather models: capacity at 5 F against 47 F)energystar.gov
Written and checked by Ali, who is not a licensed electrician.
Before you wire anything
These calculators give estimates worked out from physics and published maker data. They are not engineering, design or code advice, and they do not replace an inspection.
Electrical codes differ by edition and by town. Your local inspector, the authority having jurisdiction (AHJ), has the final say on wire size, conduit, boxes and breakers.
Mains wiring can kill and can start fires. Unless you are trained for it, hire a licensed electrician, and get a permit where your town requires one.