Mini Split Size Calculator

Size each room, pick its head, then match one outdoor unit.

By Ali (not a licensed electrician) Updated

Mini split inputs

Units
  1. Room 1

  2. Room 2

People: who usually uses the room (2 are included). Kitchen adds 4,000 BTU/h. Poorly insulated (garage, sunroom, older house): the head goes up one size.

Mitsubishi, Fujitsu and Daikin sheets allow indoor heads up to 130% of the outdoor unit's capacity. Pick 100% for another brand or if you are not sure.

Rated output

Matched

Outdoor unit

24,000BTU/h

2 tons, up to 3 zones: heads 18,000 + 9,000 BTU/h = 27,000, 113% of it (130% allowed).

  • Room 1 · 450 sq ft · kitchen: 16,000 BTU/h → 18,000 head
  • Room 2 · 280 sq ft: 7,000 BTU/h → 9,000 head
Room loads23,000 BTU/h
Indoor heads27,000 BTU/h
Heads vs outdoor113%
Smallest head2.7 ×
  • Room loads: 1.92 tons · 6.74 kW
  • Indoor heads: 18,000 + 9,000
  • Heads vs outdoor: allowed up to 130%
  • Smallest head: outdoor ÷ 9,000 head; DOE: 3 × or less

Maker charts often show a size or more bigger. Why

  • Rule-of-thumb estimate; a Manual J load calc by a pro sizes the real system.
  • When every head runs flat out together, the outdoor unit holds them to its own 24,000 BTU/h (Fujitsu); rooms rarely all peak at once.
  • Room figures assume an 8 ft ceiling (ENERGY STAR). With higher ceilings ENERGY STAR says you may want more capacity, but it gives no figure.
  • Too big a head cools before it dries the air, and the room feels damp and clammy (ENERGY STAR).
  • For heating in a cold climate, compare the outdoor unit's output at 5 F with the room total: ENERGY STAR cold-climate models keep at least 70% of their 47 F capacity there.
  • Wire and breaker come from the outdoor unit's nameplate (its minimum circuit ampacity and maximum breaker). It needs its own circuit, wired by a qualified electrician (MRCOOL's manual says so even for its DIY kits), and refrigerant work is for an EPA Section 608 certified technician.

Working

  1. Room 1: 450 sq ft → 12,000 BTU/h (ENERGY STAR, 450 up to 550 sq ft); kitchen + 4,000 = 16,000; head 18,000
  2. Room 2: 280 sq ft → 7,000 BTU/h (250 up to 300 sq ft); head 9,000
  3. Rooms: 16,000 + 7,000 = 23,000 BTU/h
  4. Outdoor: the smallest size of at least 23,000 BTU/h whose 130% holds the 27,000 of heads: 24,000 (130% = 31,200), 3 zones for 2 rooms
  5. Tons: 24,000 ÷ 12,000 = 2

Model HC-06

Room loads from the ENERGY STAR room table, as the BTU calculator. Lamp: green when the outdoor unit is 3 times the smallest head or less (DOE), amber above.

Quick answer

Two rooms of 450 sq ft (with a kitchen) and 280 sq ft need 23,000 BTU/h of cooling: an 18,000 and a 9,000 BTU/h head on one 24,000 BTU/h outdoor unit (2 tons), the heads at 113% of it.

Rule of thumbTypical: a 280 sq ft bedroom needs 7,000 BTU/h (ENERGY STAR), so a 9,000 BTU/h head; heads on one outdoor unit may total up to 130% of it.

NoteRule-of-thumb estimate; a Manual J load calc by a pro sizes the real system. The 130% limit is from makers' sheets: your model's sheet and its nameplate decide. This is an estimate from physics and maker data, not engineering or code advice. Hire a licensed HVAC contractor for the work.

Head size by room area

ENERGY STAR room capacity for an 8 ft ceiling, average sun and 2 people; the head is the smallest standard size that covers it.
Room area, sq ftCooling, BTU/hHead
100 up to 1505,0006,000
150 up to 2506,0006,000
250 up to 3007,0009,000
300 up to 3508,0009,000
350 up to 4009,0009,000
400 up to 45010,00012,000
450 up to 55012,00012,000
550 up to 70014,00015,000
700 up to 1,00018,00018,000
1,000 up to 1,20021,00024,000
1,200 up to 1,40023,00024,000
1,400 up to 1,50024,00024,000
1,500 and upOver 24,000: two heads or a ducted unit

Outdoor unit sizes and zones

Zones from Mitsubishi, LG, Fujitsu and Daikin sheets (makers differ: check your model); the 130% limit from Mitsubishi, Fujitsu and Daikin.
Outdoor unit, BTU/hTonsZones, up toHeads at 130%
18,0001.5223,400
24,0002331,200
30,0002.5439,000
36,0003446,800
42,0003.5554,600
48,0004862,400
60,0005878,000

How to size a multi-zone mini split, room by room

Size each room on its own, give it the smallest head that covers it, then take the smallest outdoor unit that covers the rooms’ total: an open living room and kitchen of 450 sq ft and a 280 sq ft bedroom need 23,000 BTU/h, an 18,000 and a 9,000 BTU/h head, and a 24,000 BTU/h outdoor unit.

A head is the indoor unit on the wall; the outdoor unit, or condenser, feeds every head. Each head serves one zone, a room with its own thermostat. A ton is 12,000 BTU/h, so 24,000 is 2 tons. The heads’ total, the connected capacity, must stay inside the maker’s limit: 27,000 is under 130% of 24,000.

The page opens on two rooms. To size one room, press the X on Room 2 (Remove room 2); the answer is then that room’s head on its own outdoor unit.

Mini split BTU per room: the ENERGY STAR table

Each room’s BTU/h comes from the ENERGY STAR room table the BTU calculator uses: 6,000 BTU/h for 150 up to 250 sq ft with an 8 ft ceiling, 10% less if heavily shaded, 10% more if very sunny, 600 more for each person past two and 4,000 more for a kitchen.

Both pages agree: a 280 sq ft bedroom is 7,000 BTU/h on each. ENERGY STAR gives no figure for a higher ceiling, so this calculator adds nothing for height. Pioneer’s sizing guide adds about 10% per foot above 8 ft; for a taller room, raise that room’s load by hand and pick the head from the head table. A garage, sunroom or poorly insulated room keeps its load but gets the next head size up, as Carrier, Pioneer and MRCOOL advise.

Why maker charts show bigger heads

At 200 sq ft the ENERGY STAR table gives 6,000 BTU/h, Carrier’s chart 6,000 to 9,000 and Pioneer’s and MRCOOL’s 9,000, so their charts start a head size or more higher.

A head that is too big cools the room before it dries the air, so the room feels damp and clammy (ENERGY STAR, NRCan). DOE adds that room-by-room loads can be surprisingly small.

Matching heads to one outdoor unit: the 130% rule

The heads on one outdoor unit may add up to 130% of its capacity on Mitsubishi, Fujitsu and Daikin multi-zone systems: Mitsubishi’s 48,000 BTU/h MXZ-8C48NA takes 12,000 to 62,400 BTU/h of indoor units.

Rooms seldom peak at once, and Fujitsu says that when every head runs flat out, the system holds their total to the outdoor unit’s capacity. For another brand, set the calculator to 100%. Each outdoor size also runs a set number of zones, so five small rooms can need a bigger unit than their load alone. Mitsubishi’s units need at least 2 indoor units.

Small rooms on a big outdoor unit: the 3 times rule

Keep the outdoor unit at no more than 3 times the smallest head when its minimum output is unknown, DOE’s cold-climate sizing guide says: a 30,000 BTU/h unit serving a 6,000 BTU/h bedroom head is 5 times.

An outdoor unit slows down only so far: Mitsubishi’s 24,000 BTU/h MXZ-3C24NAHZ heats from 7,200 BTU/h, and LG’s LMU24CHV cools from 8,400. Below that a small room gets too much, so the unit cycles on and off, and the lamp turns amber. DOE’s answer is more, smaller outdoor units.

Heating in cold weather: read the 5 F capacity

Cold-climate heat pumps keep at least 70% of their 47 F heating capacity at 5 F (ENERGY STAR), so compare that 5 F figure, not the rated one, with your rooms.

PNNL’s guide uses the same 70% line. The room loads here are cooling figures; a cold-climate heating load needs a load calculation. For running costs against gas, use the heat pump calculator.

Wiring, refrigerant and the Manual J load calc

The outdoor unit’s wire and breaker come from its nameplate: Mitsubishi lists a 29.9 A minimum circuit ampacity and a 40 A breaker for its MXZ-3C24NAHZ, and LG 13.3 A and 20 A for its LMU18CHV.

Minimum circuit ampacity (MCA) is the least current the circuit’s wire must be rated for. Size its wire and breaker with the wire size calculator and the breaker size calculator. The unit needs its own circuit, wired by a qualified electrician, as MRCOOL’s manual says even for its DIY kits. Refrigerant work is for a technician certified under EPA Section 608. This page gives a rule-of-thumb estimate; a Manual J load calc by a pro sizes the real system.

Worked example

  1. Inputs: room 1, 450 sq ft, average sun, 2 people, kitchen; room 2, 280 sq ft, average sun, 2 people; heads may total 130% of the outdoor unit.
  2. Room 1: 450 sq ft → 12,000 BTU/h (ENERGY STAR, 450 up to 550 sq ft); kitchen + 4,000 = 16,000; head 18,000
  3. Room 2: 280 sq ft → 7,000 BTU/h (250 up to 300 sq ft); head 9,000
  4. Rooms: 16,000 + 7,000 = 23,000 BTU/h
  5. Outdoor: the smallest size of at least 23,000 BTU/h whose 130% holds the 27,000 of heads: 24,000 (130% = 31,200), 3 zones for 2 rooms
  6. Tons: 24,000 ÷ 12,000 = 2

Questions people ask

What size mini split do I need for a 400 sq ft room?

A 12,000 BTU/h head: ENERGY STAR puts a 400 sq ft room at 10,000 BTU/h with an 8 ft ceiling, and 12,000 is the next head size. Maker charts start higher (Carrier 12,000 to 15,000, Pioneer 18,000); a Manual J load calc by a pro settles it.

Can the indoor units add up to more than the outdoor unit?

Yes, up to 130% on Mitsubishi, Fujitsu and Daikin multi-zone systems: Fujitsu's 48,000 BTU/h outdoor unit takes 62,000 BTU/h of heads. When every head runs at once, the outdoor unit holds the total to its own capacity (Fujitsu).

How many zones can one outdoor unit run?

2 to 8: LG's 18,000 BTU/h unit runs 2, its 24,000 unit up to 3, its 30,000 and 36,000 units up to 4, Mitsubishi's MXZ-5C42NA 5, and 48,000 BTU/h units from Mitsubishi, Fujitsu, LG and Daikin up to 8. DOE's guide says to pick by the room loads, not the number of zones.

Is a bigger outdoor unit better?

No: keep it at 3 times the smallest head or less when its minimum output is unknown, DOE's cold-climate guide says, so a 24,000 BTU/h unit suits heads of 9,000 BTU/h and up. A unit that can't slow down enough for a small room cycles on and off; use more, smaller outdoor units.

Do mini splits heat in very cold weather?

Cold-climate models keep at least 70% of their 47 F heating capacity at 5 F (ENERGY STAR): Mitsubishi lists 25,000 BTU/h at 5 F for its MXZ-3C24NAHZ, all of its rated 25,000. A model short of that mark keeps less: LG lists 14,807 of 22,000 (67%) for its LMU18CHV. In a cold climate, compare the 5 F figure with your rooms.

Related guides

Sources

Data last verified: Page updated

Built and checked by Ali, who is not a licensed electrician.