Wattplate

Heat Pump Cost Calculator

Yearly running cost against a gas furnace and electric heat.

Heat figure from
Bill shows

80%: mid-efficiency, DOE. The furnace label or manual gives yours.

HSPF2 7.8: ENERGY STAR split.

Prices: 18.19 ¢/kWh, $1.48/therm

US average 18.19 ¢: EIA, January-July 2026 (preliminary). The rate on your bill is better.

US average $1.48: EIA, 2025 average. Use the per-therm total on your bill, delivery included.

More: bill helper off · HSPF2 7.8 · cooling off

Heating gas from a year of bills

Gas for heating only: the year minus what water heating and cooking use. Bills print therms or ccf.

Heating gas = whole year − 12 × one summer month. This assumes summer gas (water heating and cooking) is the same all year.

Heat pump rating

Heat pump rated by

Cooling (optional)

Old rating is

SEER2 15.2: ENERGY STAR split.

AC kWh: summer bills above a spring month. Labels from before 2023 print SEER, newer ones SEER2.

Rated output

Estimate

Heat pump, a year

$1,493

At these prices the gas furnace costs $309 a year less than the heat pump.

Break-even with the gas furnace

Costs match at 14.4 ¢/kWh, at $1.87/therm or at HSPF2 9.8 (COP 2.88). The heat pump wins at a lower electricity price, a higher gas price or a higher rating.

Gas furnace, a year$1,184
Resistance heat, a year$3,412
Heat delivered64.0 MMBtu
Heat pump uses8,205 kWh
Seasonal COP2.29
Gas at 80% AFUE800 therms

64.0 MMBtu of heat; heat pump 8,205 kWh at a seasonal COP of 2.29

Prices: electricity 18.19 ¢/kWh, US average, EIA, January-July 2026 (preliminary); gas $1.48/therm, US average, EIA, 2025 average.

HSPF2 is a moderate-climate rating; cold-climate field studies measured seasonal COPs of 1.9 (Minnesota, whole system with backup heat) and 2.5 (12 cold-climate homes, compressor only, NREL).

Backup heat and duct losses are not modelled.

Working

  1. Heat = gas × 100,000 Btu × AFUE = 800 therms × 100,000 Btu × 0.80 = 64,000,000 Btu (64.0 MMBtu)
  2. Seasonal COP = HSPF2 ÷ 3.412 = 7.8 ÷ 3.412 = 2.29
  3. Heat pump energy = heat ÷ (HSPF2 × 1,000) = 64,000,000 Btu ÷ (7.8 × 1,000) = 8,205.1 kWh
  4. Heat pump cost = 8,205.1 kWh × $0.1819 = $1,493
  5. Gas furnace cost = 800 therms × $1.48 = $1,184
  6. Resistance heat energy = heat ÷ 3,412 = 64,000,000 Btu ÷ 3,412 = 18,757.3 kWh
  7. Resistance heat cost = 18,757.3 kWh × $0.1819 = $3,412
  8. Break-even rate = gas cost ÷ heat pump kWh = $1,184 ÷ 8,205.1 kWh = 14.4 ¢/kWh
  9. Break-even COP = rate × AFUE × 29.31 ÷ gas price = $0.1819 × 0.80 × 29.31 ÷ $1.48 = 2.88 (HSPF2 9.8)

Model HC-05

Estimate, not a Manual J. A load calculation by a pro sizes the real system.

Quick answer

At 18.19 ¢/kWh and $1.48/therm, a heat pump rated HSPF2 7.8 costs about $1,493 a year for the 64.0 MMBtu of heat that 800 therms of gas give in an 80% furnace; the furnace costs $1,184.

Rule of thumbTypical: 800 therms in an 80% furnace = 64.0 MMBtu of heat; a heat pump at HSPF2 7.8 needs 8,205 kWh for it.

NoteEstimate, not a Manual J. A load calculation by a pro sizes the real system; label ratings are moderate-climate averages. This is an estimate from physics and maker data, not engineering or code advice. Hire a licensed HVAC contractor for the work.

Cost of 1 MMBtu of heat at US average prices
SystemRatingPer MMBtu
Gas furnace80% AFUE$18.50
Gas furnace90% AFUE$16.44
Gas furnace95% AFUE$15.58
Gas furnace97% AFUE$15.26
Heat pumpHSPF2 7.5 (COP 2.20)$24.25
Heat pumpHSPF2 7.8 (COP 2.29)$23.32
Heat pumpHSPF2 8.5 (COP 2.49)$21.40
Heat pumpHSPF2 10 (COP 2.93)$18.19
Electric resistanceCOP 1$53.31

Electricity 18.19 ¢/kWh: US average, EIA, January-July 2026 (preliminary). Gas $1.48/therm: US average, EIA, 2025 average. 1 MMBtu is 1,000,000 Btu, the energy in 10 therms of gas.

How the calculator compares the three costs

Every system in the comparison has to put the same heat into your home, so the calculator starts by working out that heat in Btu. Pick where your figure comes from:

  • Gas bill: the therms your furnace burns for heating in a year, times 100,000 Btu per therm, times the furnace’s AFUE. 800 therms in an 80% furnace deliver 64,000,000 Btu (64.0 MMBtu) of heat.
  • Electric heat: the kWh a year your baseboard heaters or electric furnace use, times 3,412 Btu per kWh. Resistance heat turns each kWh into 3,412 Btu.
  • Heat load: the heat in MMBtu a year, if you already know it. 1 MMBtu is 1,000,000 Btu.

Then it prices that heat three ways. A heat pump needs heat ÷ (HSPF2 × 1,000) kWh. A gas furnace needs heat ÷ (100,000 × AFUE) therms. Electric resistance heat needs heat ÷ 3,412 kWh. Each one is multiplied by your price, and the rating plate shows the three yearly costs side by side, with every step in the working.

Finding your heating gas on a bill

A gas bill counts every therm: the furnace, the water heater and the stove. Only the furnace’s share belongs here. A common way to find it is to take the whole year’s gas and subtract 12 times one summer month, when the furnace is off. The “Work it out from a year of bills” panel does this sum for you and prints it. It assumes water heating and cooking use the same gas all year, which is close enough for an estimate.

Some utilities bill in ccf (hundred cubic feet) instead of therms. Pick Ccf and the calculator converts at 1.037 therms per ccf, the US average heat content of natural gas in 2025 (EIA). For the price, use what one therm costs you with delivery charges included, not just the supply line.

Where the answer flips

The plate also shows the break-even points. For the example above, the heat pump costs less to run than the 80% furnace once electricity drops below 14.4 ¢/kWh, once gas rises above $1.87 a therm, or once its rating passes about HSPF2 9.8 (COP 2.88). The idea behind it: a therm of gas holds as much energy as 29.31 kWh of electricity, so the heat pump wins when its COP is high enough to cover the price gap between the two fuels after the furnace’s losses.

A rating is not your winter

HSPF2, the heating rating on heat pump labels since 2023, is a season-long average for a moderate climate. Divide it by 3.412 for the seasonal COP the calculator uses: HSPF2 7.8 is a COP of 2.29, so each kWh of electricity moves about 2.29 kWh of heat into the house. In a hard winter the real figure is lower. A Minnesota field study measured an annual COP of 1.9 for whole all-electric systems, backup heat included, and NREL measured 2.5 for the compressor alone in 12 cold-climate homes. If your winters are cold, switch the rating to COP and try a lower number. Backup heat strips and duct losses are not modelled.

Cooling

If the heat pump will also replace an air conditioner, open “Cooling too” and enter what the old unit uses in a year and its rating. The new unit’s kWh = old kWh × old rating ÷ new SEER2. Ratings printed before 2023 are SEER, a different test from SEER2, so that saving is only a rough guide.

What this page leaves out

It estimates running costs from your bills and your prices. It does not size a heat pump, choose a model, price the installation or count incentives, and it does not cover propane, oil or ground-source systems. Sizing takes a contractor’s load calculation.

Worked example

  1. Inputs: 800 therms of heating gas a year in an 80% AFUE furnace; electricity 18.19 ¢/kWh; gas $1.48/therm; heat pump HSPF2 7.8.
  2. Heat = gas × 100,000 Btu × AFUE = 800 therms × 100,000 Btu × 0.80 = 64,000,000 Btu (64.0 MMBtu)
  3. Seasonal COP = HSPF2 ÷ 3.412 = 7.8 ÷ 3.412 = 2.29
  4. Heat pump energy = heat ÷ (HSPF2 × 1,000) = 64,000,000 Btu ÷ (7.8 × 1,000) = 8,205.1 kWh
  5. Heat pump cost = 8,205.1 kWh × $0.1819 = $1,493
  6. Gas furnace cost = 800 therms × $1.48 = $1,184
  7. Resistance heat energy = heat ÷ 3,412 = 64,000,000 Btu ÷ 3,412 = 18,757.3 kWh
  8. Resistance heat cost = 18,757.3 kWh × $0.1819 = $3,412
  9. Break-even rate = gas cost ÷ heat pump kWh = $1,184 ÷ 8,205.1 kWh = 14.4 ¢/kWh
  10. Break-even COP = rate × AFUE × 29.31 ÷ gas price = $0.1819 × 0.80 × 29.31 ÷ $1.48 = 2.88 (HSPF2 9.8)
  11. At these prices the gas furnace costs $309 a year less than the heat pump.
  12. Costs match at 14.4 ¢/kWh, at $1.87/therm or at HSPF2 9.8 (COP 2.88). The heat pump wins at a lower electricity price, a higher gas price or a higher rating.

Questions people ask

Is a heat pump cheaper to run than a gas furnace?

It depends on your two prices and on how efficient the heat pump really is. At the US averages, electricity 18.19 ¢/kWh (EIA, January-July 2026, preliminary) and gas $1.48 a therm (EIA, 2025 average), a heat pump needs a seasonal COP of about 2.88 (HSPF2 9.8) to match an 80% furnace. At HSPF2 7.8 (COP 2.29) the furnace costs $309 a year less for 800 therms of heating gas. Where electricity is cheap or gas is dear, the heat pump wins, so type the prices from your own bills.

What do COP, HSPF2 and SEER2 mean?

COP is heat out divided by electricity in, both in the same unit: at a COP of 3, each kWh of electricity delivers 3 kWh of heat, and resistance heat has a COP of 1. HSPF2 is a whole heating season in Btu per watt-hour of electricity, rated for a moderate climate; divide it by 3.412 for the seasonal COP (HSPF2 7.8 is 2.29). SEER2 is the same kind of ratio for cooling. HSPF2 and SEER2 replaced HSPF and SEER on January 1, 2023 (DOE), and the old and new numbers are not on the same scale.

How much does a heat pump save over baseboard heat or an electric furnace?

DOE says a modern air-source heat pump can cut electricity use by about 50% compared with baseboard heaters and electric furnaces. The share saved is 1 − 1/COP: at HSPF2 8.5 (COP 2.49) a heat pump uses about 60% less electricity than resistance heat for the same warmth. For 12,000 kWh of baseboard heat a year at the US average rate, that is about $1,307 a year.

What is AFUE?

Annual fuel utilization efficiency: the share of the gas energy that ends up as heat in your home over a year. An 80% AFUE furnace gives 80 Btu of heat for every 100 Btu of gas. DOE puts old furnaces at 56-70%, mid-efficiency models at 80-83% and high-efficiency models at 90-98.5%. ENERGY STAR gas furnaces reach 95% or more in the South and 97% or more in the North. The AFUE is on the furnace label or in its manual.

Do heat pumps work in cold weather?

Yes, but they get less efficient as it gets colder, and many lean on backup heat on the coldest days. ENERGY STAR cold-climate heat pumps must still reach a COP of 1.75 at 5 °F. In the field, NREL measured a seasonal COP of 2.5 on average (1.7 to 3.5) for the compressor alone in 12 cold-climate homes, and a Minnesota study measured 1.9 on average for whole all-electric systems, backup heat included. If your winters are cold, switch the rating to COP and try a figure in that range.

Is this the same as a Manual J?

No. This is an operating-cost estimate from your own bills and prices. A Manual J is a room-by-room load calculation that a contractor uses to size a system, and this page does not size equipment.

Sources

Data last verified: Page updated

Written and checked by Ali, who is not a licensed electrician.

Before you wire anything

These calculators give estimates worked out from physics and published maker data. They are not engineering, design or code advice, and they do not replace an inspection.

Electrical codes differ by edition and by town. Your local inspector, the authority having jurisdiction (AHJ), has the final say on wire size, conduit, boxes and breakers.

Mains wiring can kill and can start fires. Unless you are trained for it, hire a licensed electrician, and get a permit where your town requires one.