CFM Calculator
Airflow for a room, a bath fan, a range hood or an HVAC system.
HVI: a complete air change about 8 times an hour.
Add up the burners on the rating label.
350 for humid climates, 450 for dry. The equipment manual wins.
Supply air versus return air; about 20 °F (11 °C) is common for cooling.
Rated output
No readingAirflow needed
96CFM
720 ft³ at 8 air changes an hour needs 96 CFM. Buy a fan of at least 100 CFM.
CheckLast good result. Check the field above.
- Rule of thumb: the fan or vent label rating wins. Fan and hood ratings are in CFM.
Working
- Volume = 10 × 8 × 9 ft = 720 ft³
- Airflow = 720 ft³ × 8 ÷ 60 = 96.0 CFM
- Fan size = 96.0 CFM rounded up to the next 10 = 100 CFM
Model HC-02
Rule-of-thumb estimate. Fan and hood ratings, your equipment's manual and local code decide; a pro's load and duct design sizes HVAC airflow. Amber only for a range hood above 400 CFM (make-up air, IRC M1503); the other cards have no sourced limit.
Quick answer
A 720 ft³ room at 8 air changes an hour needs 96 CFM (45.3 L/s), so buy a fan of at least 100 CFM.
Rule of thumbTypical: CFM = room volume × air changes per hour ÷ 60: a 10 × 8 × 9 ft bathroom at 8 is 96 CFM, so buy 100.
NoteRule-of-thumb estimate. Fan and hood ratings, your equipment's manual and local code decide; a pro's load and duct design sizes HVAC airflow. This is an estimate from physics and maker data, not engineering or code advice. Hire a licensed HVAC contractor for the work.
| Area | × 0.13 | HVI |
|---|---|---|
| 40 sq ft | 41.6 | 50 |
| 60 sq ft | 62.4 | 60 |
| 80 sq ft | 83.2 | 80 |
| 100 sq ft | 104 | fixtures |
Volume × 0.13 is the Broan figure. From 100 sq ft the HVI rule adds fixtures instead. The fan is the larger figure, rounded up to the next 10.
| Burners | Gas rule |
|---|---|
| 30,000 BTU/h | 300 |
| 45,000 BTU/h | 450 |
| 60,000 BTU/h | 600 |
| 90,000 BTU/h | 900 |
BTU/h ÷ 100. The HVI per-foot figure for your range width can be higher; the calculator takes the larger.
| Tons | 350 | 400 | 450 |
|---|---|---|---|
| 1.5 | 525 | 600 | 675 |
| 2 | 700 | 800 | 900 |
| 2.5 | 875 | 1,000 | 1,125 |
| 3 | 1,050 | 1,200 | 1,350 |
| 4 | 1,400 | 1,600 | 1,800 |
| 5 | 1,750 | 2,000 | 2,250 |
Your equipment's install manual sets the real airflow.
What CFM means
CFM is cubic feet per minute: how much air a fan, a hood or a duct moves. The calculator has four cards, because the question changes with the room. The room card turns a volume and a number of air changes into airflow. The bath fan card follows the HVI rule and the Broan volume method. The range hood card uses burner heat and the width of the range. The HVAC card links airflow, heat and tons.
Every card prints its working with your numbers, so you can check it by hand. Metric mode shows litres per second, metres, kilowatts and °C beside the fan rating in CFM.
Room airflow from air changes
The room formula is volume times air changes per hour, divided by 60. An air change is one full volume of the room replaced each hour. The chips set the usual starting points: 8 for a bathroom (HVI), 15 for a kitchen under the older HVI rule, and 0.35 for whole-house ventilation (ASHRAE 62.2, quoted by the EPA). You can type any figure from 0.1 to 60.
A fan is sold in steps, so the answer shows the exact airflow and a buy size rounded up to the next 10 CFM. A fan below the exact figure moves less air than the room needs, so the buy size is never lower.
Bath fan size
HVI gives two cases. Under 100 square feet, use 1 CFM per square foot with a floor of 50 CFM. From 100 square feet, add up the fixtures: 50 for a toilet, 50 for a shower, 50 for a bathtub and 100 for a jetted tub. A bathroom of exactly 100 square feet uses the fixtures.
Broan’s help page gives a second method that adds ceiling height: volume in cubic feet times 0.13, rounded up. The card shows both and sizes the fan to the larger. A high ceiling pushes the volume figure above the HVI one.
Range hood CFM
Two rules apply, and the card takes the larger. The first is for gas ranges: add the BTU/h of every burner and divide by 100, which is the rule Proline and World Coppersmith print. The second is HVI’s guidance per linear foot of range, which depends on where the hood sits: 100 against a wall and 150 over an island as the recommended figure, 40 and 50 as the minimum.
Electric ranges use the HVI per-foot figure alone. If you add the kitchen size, the card also shows the older rule of 15 air changes an hour as a cross-check. It never sets the answer, because HVI’s current guidance is per foot of range.
These are guidance figures, not a code requirement. One thing the code does say: a hood that can move more than 400 CFM may need make-up air. The lamp turns amber above that figure as a reminder to check local code and any fuel-burning appliance in the home.
HVAC airflow
For cooling and heating, the sensible heat in air is 1.08 times the CFM times the temperature difference in °F. The 1.08 comes from the density and specific heat of air at 70 °F near sea level, and ACCA points out it is not a true constant: it falls with altitude. The card turns BTU/h into CFM and back, and shows the tons (12,000 BTU/h each).
The third mode multiplies tons by CFM per ton. The usual figure is 400, with 350 for humid climates and 450 for dry ones. Treat the answer as a range: your air handler’s install manual sets the airflow for your equipment, and a pro’s Manual J load calculation and duct design size the system. The calculator does not do either.
What it leaves out
This is a rule-of-thumb estimate for a single room, fan or hood. It does not count duct length or elbows, which cut real airflow, and it has no fan curves, no altitude correction, no downdraft sizing and no make-up air sizing. It also has no engine or carburetor CFM, which is a different question.
Fan and hood ratings on the label, your equipment’s manual and your local code decide the final choice.
Worked example
- Inputs: 10 × 8 × 9 ft room at 8 air changes an hour.
- Volume = 10 × 8 × 9 ft = 720 ft³
- Airflow = 720 ft³ × 8 ÷ 60 = 96.0 CFM
- Fan size = 96.0 CFM rounded up to the next 10 = 100 CFM
Questions people ask
How do you calculate CFM for a room?
Multiply length by width by height for the volume in cubic feet, multiply by the air changes per hour you want, and divide by 60. A 10 × 8 ft bathroom with a 9 ft ceiling at 8 air changes an hour needs 720 × 8 ÷ 60 = 96 CFM, so a 100 CFM fan covers it.
What size bathroom fan do I need?
HVI says 1 CFM per square foot for a bathroom under 100 square feet, and at least 50 CFM. From 100 square feet, add 50 CFM for each toilet, shower and bathtub and 100 for a jetted tub. Broan also multiplies the room volume by 0.13 and rounds up to the next 10. The calculator uses the larger of the two.
How many CFM does a range hood need?
For gas, divide the total burner BTU/h by 100 (Proline, World Coppersmith): a 60,000 BTU/h range needs 600 CFM. HVI also gives 100 CFM per foot of range against a wall and 150 over an island. Above 400 CFM, if the home has a fuel-burning appliance that is not direct-vent or power-vented (such as a natural-draft water heater or furnace), the IRC (section M1503) calls for make-up air. Check local code.
How many CFM per ton of air conditioning?
About 400, with 350 for humid climates and 450 for dry ones; those are the three settings on a Trane air handler board. ACCA says the equipment manual sets the real airflow, so use this only as a range.
How do I convert BTU/h to CFM?
CFM = BTU/h ÷ (1.08 × the air temperature difference in °F). 24,000 BTU/h across a 20 °F difference is 1,111 CFM. The 1.08 is for air near sea level and 70 °F and shrinks at altitude.
How many CFM is 100 L/s?
100 L/s is 212 CFM: divide litres per second by 0.4719474. Going the other way, multiply CFM by 0.4719474.
Sources
- HVI: How Much Ventilation Do I Need?hvi.org
- Broan-NuTone help: sizing a bathroom exhaust fanbroan-nutone.com
- Ask the Builder: Sizing an Exhaust Fanaskthebuilder.com
- Proline Range Hoods: How many CFM do I needprolinerangehoods.com
- World Coppersmith: How much CFM does a range hood needworldcoppersmith.com
- Penn State PHRC Builder Brief BB0412: Kitchen ventilation, makeup airpsu.edu
- Green Building Advisor: Makeup air for kitchen exhaustgreenbuildingadvisor.com
- HVAC School: Sensible Heat in Air and Waterhvacrschool.com
- ACCA blog: Hey Ed, what is the correct airflow for an ACacca.org
- EPA: How much ventilation do I need in my homeepa.gov
Written and checked by Ali, who is not a licensed electrician.
Before you wire anything
These calculators give estimates worked out from physics and published maker data. They are not engineering, design or code advice, and they do not replace an inspection.
Electrical codes differ by edition and by town. Your local inspector, the authority having jurisdiction (AHJ), has the final say on wire size, conduit, boxes and breakers.
Mains wiring can kill and can start fires. Unless you are trained for it, hire a licensed electrician, and get a permit where your town requires one.