Wattplate

Voltage Drop Calculator

The drop, the volts at the load and the smallest wire for your run.

Voltage drop inputs

Units

= 3.31 mm²

Hotter wire has more resistance. 75 °C (the default) suits a loaded wire; a lightly loaded one runs cooler.

Metal
System

Rated output

Over 5%

Voltage drop

7.88V

12 AWG copper, 100 ft at 20 A on 120 V: the drop is 7.88 V (6.57%), over the 3% limit.

Over the limit6.57% drop

Over 5%, more than most circuits are meant to lose.

Use a larger wire or a shorter run; 8 AWG copper keeps it within 3%.

Drop6.57%
Supply120 V
At the load112.12 V
Run at 3%45 ft
Smallest wire8 AWG
Heat158 W

Smallest wire for 3%: 8 AWG copper, 8.37 mm². 2.60% drop.

Working

  1. Resistance of 12 AWG copper at 75 °C, stranded: 1.9701 Ω per 1,000 ft
  2. Drop = 2 × 100 ft × 20 A × 1.9701 Ω ÷ 1,000 = 7.88 V
  3. Drop % = 7.88 V ÷ 120 V × 100 = 6.57%
  4. At the load = 120 V − 7.88 V = 112.12 V
  5. Heat = 2 × 20 A × 20 A × 100 ft × 1.9701 Ω ÷ 1,000 = 158 W
  6. Longest run at 3% = 3% × 120 V × 1,000 ÷ (2 × 20 A × 1.9701 Ω) = 45 ft

Model WV-02

Typical figures from physics for stranded wire, resistance only. Lamp: green within 3%, amber over it, red over 5% (or your limit, if higher). The 3% branch and 5% total are informational notes in NEC 210.19(A) and 215.2(A): suggestions, not rules. Check your code edition and your local inspector (AHJ).

Quick answer

20 A over 100 ft of 12 AWG copper wire on a 120 V circuit drops 7.88 V (6.57%), leaving 112.12 V at the load. The smallest wire that keeps the drop within 3% is 8 AWG copper.

Rule of thumbAt 20 A on 120 V, 12 AWG copper drops about 6.6% over 100 ft; 8 AWG keeps it under 3%.

NoteTypical figures. Check your code edition and your local inspector (AHJ). This is an estimate from physics and maker data, not engineering or code advice. Hire a licensed electrician for the work.

Voltage drop per 100 ft at 20 A, copper, 75 °C
Wire120 V240 VRun at 3%
12 AWG6.57%3.28%45 ft
10 AWG4.13%2.07%72 ft
8 AWG2.60%1.30%115 ft
6 AWG1.63%0.82%183 ft
4 AWG1.03%0.51%292 ft

Single phase, stranded copper. Each drop is for a one-way run of 100 ft; the last column is the longest run on 120 V before the drop reaches 3%. 14 AWG copper is limited to 15 A circuits.

How voltage drop works

Every wire has a little resistance. When current flows, part of the voltage is used up pushing that current along the wire, so the load at the far end gets less than the panel or battery sends. That loss is the voltage drop. It grows with the current, the length of the run and the temperature of the wire, and it shrinks as the wire gets thicker.

A small drop is normal. A large one makes motors run hot and slow and upsets electronics, and the lost voltage turns into heat in the wire itself. The calculator shows that heat in watts, so you can see what a thin wire costs you.

The formula, step by step

The calculator works from the physics of the wire, the same method an electrician uses with a pocket calculator:

  1. Resistance. It finds the cross-section of the wire from its AWG or kcmil size, then its resistance per 1,000 ft from the metal: copper, or aluminum with about 61% of the conductivity of copper. It corrects for temperature and adds 2% for stranded wire, because the strands spiral and are a little longer than the cable.
  2. Drop. Drop = 2 × one-way length × amps × resistance ÷ 1,000. The 2 counts the trip out and back. A balanced three phase circuit uses 1.732 instead of 2, with the volts measured line to line.
  3. Percent. The drop divided by the source voltage, times 100.
  4. Longest run. The same formula turned around: how far this wire can go before the drop reaches your limit.

The worked example below runs these steps for the numbers the calculator opens with: 20 A over 100 ft of 12 AWG copper on 120 V drops 7.88 V, leaving 112.12 V at the load.

How much drop is acceptable

The National Electrical Code suggests, in informational notes, about 3% on a branch circuit and 5% in total for a feeder and branch together. Those notes are advice, not rules, and most electricians design to them anyway. Equipment makers and local rules can be stricter, so read the nameplate and ask your inspector.

Low-voltage systems use their own figures. Marine practice allows 3% for anything that affects safe operation and 10% for the rest, and solar installers aim for about 2% between the panels and the batteries. The chips under the limit box fill in these figures for you.

Choosing the smallest wire

Distance is only half of the answer. A short run with a heavy load can pass a 3% test on a wire that is far too small to carry the current without overheating. So the smallest wire shown is never below its typical current rating at 60 °C, the figure used for most home circuits of 100 A or less. When that rating sets the size instead of the distance, the result says so. If the wire you picked is below its typical rating for your load, a red line names the limit, such as 15 A for 14 AWG copper.

Above 100 A the calculator still finds the smallest wire for the drop, but you need to check the current rating separately. To size a whole circuit from its load or its breaker, including loads that run for hours, use the wire size calculator.

Low-voltage DC: RVs, vans, boats and solar

At 12 V every tenth of a volt matters: 3% of 12 V is only 0.36 V. That is why battery cables are so thick and the runs so short. Moving the system to 24 V halves the current for the same power and doubles the volts your limit allows, so the same wire can carry the load about four times as far. Pick DC, enter the one-way distance from the battery to the load, and the calculator counts both wires.

What this calculator leaves out

It uses resistance only. On AC, large wires add reactance and skin effect, more so in steel conduit, so for 1/0 AWG and up the real drop can be higher than shown, and the result says so. It does not model parallel sets of wires, the dip when a motor starts, or power factor. For those jobs, and for feeders and services, ask a licensed electrician.

Worked example

  1. Inputs: 20 A, 100 ft one way, 12 AWG copper at 75 °C, single phase 120 V, 3% limit.
  2. Resistance of 12 AWG copper at 75 °C, stranded: 1.9701 Ω per 1,000 ft
  3. Drop = 2 × 100 ft × 20 A × 1.9701 Ω ÷ 1,000 = 7.88 V
  4. Drop % = 7.88 V ÷ 120 V × 100 = 6.57%
  5. At the load = 120 V − 7.88 V = 112.12 V
  6. Heat = 2 × 20 A × 20 A × 100 ft × 1.9701 Ω ÷ 1,000 = 158 W
  7. Longest run at 3% = 3% × 120 V × 1,000 ÷ (2 × 20 A × 1.9701 Ω) = 45 ft

Questions people ask

What voltage drop is acceptable?

The code suggests, but does not require, about 3% on a branch circuit and 5% for a feeder and branch together (informational notes to 210.19(A) and 215.2(A)(1)). Some equipment and some local rules set their own limit, so check the nameplate and your local inspector (AHJ).

Why is the length doubled?

Current flows out on one wire and back on another, so the resistance that counts is the round trip. The formula multiplies the one-way length by 2. A balanced three phase circuit uses 1.732 instead of 2, with the voltage measured line to line.

Copper or aluminum, how much does it matter?

Aluminum has about 61% of the conductivity of copper, so the same size drops about 1.64 times as much. To match a copper run you usually go up about two sizes in aluminum; the calculator gives the exact figure for your run.

What does a hot wire change?

The resistance of copper rises about 0.39% for each degree C. Stranded 12 AWG copper has 1.97 ohms per 1,000 ft at 75 °C against 1.62 at 20 °C, about 22% more. Loaded wire runs warm, so the calculator starts at 75 °C; pick a lower figure for a lightly loaded run.

Which limit should I use for a 12 V RV, van or solar run?

Marine practice is 3% for anything that affects safe operation and 10% for other loads; solar guidance is about 2% from the panels to the batteries. At 12 V, 3% is only 0.36 V, so runs are short and wire is thick.

Is the result exact for large AC feeders?

No. It uses the resistance of the wire only. On AC, reactance and skin effect add to the drop on large wires, from 1/0 AWG up and more in steel conduit, so the real drop can be higher than shown. Ask an electrician for those runs.

Sources

Data last verified: Page updated

Written and checked by Ali, who is not a licensed electrician.

Before you wire anything

These calculators give estimates worked out from physics and published maker data. They are not engineering, design or code advice, and they do not replace an inspection.

Electrical codes differ by edition and by town. Your local inspector, the authority having jurisdiction (AHJ), has the final say on wire size, conduit, boxes and breakers.

Mains wiring can kill and can start fires. Unless you are trained for it, hire a licensed electrician, and get a permit where your town requires one.