HP to Amps Calculator

Motor running amps from horsepower: three-phase, single-phase or DC.

By Ali (not a licensed electrician) Updated

HP to amps inputs

Motor
Size unit

The HP on the nameplate. Fractions work: 1/2, 3/4, 1 1/2.

The nameplate voltage: most read 230/460 V. On a 208 V supply pick 208.

Blank uses 89.5%, typical for a 5 hp motor (NEMA NOM. EFF on most nameplates).

Blank uses 0.82, typical for a 5 hp, 1,800 rpm motor. A 3,600 rpm motor runs higher: type the nameplate's PF.

Rated output

Typical motor

Full-load current, each line

6.4A

A 5 hp three-phase motor on 460 V draws about 6.4 A at full load.

Power in4.17 kW · 5.08 kVA
Efficiency · PF89.5% · 0.82, typical 5 hp
Starting, for a moment40.8 to 47.8 A
Same motor at230 V: 12.8 A · 460 V: 6.4 A
  • Starting current: 6.4 to 7.5 times the running amps, for a moment as the motor starts (makers' locked-rotor data).

Working

  1. Output: 5 hp × 745.7 W = 3,728.5 W
  2. Input: 3,728.5 W ÷ 0.895 = 4,165.9 W
  3. Amps: 4,165.9 W ÷ (1.732 × 460 V × 0.82) = 6.4 A
  4. kVA: 4.17 kW ÷ 0.82 = 5.08 kVA

Model PL-08

Running amps at full load and nameplate voltage, from typical motor figures; the nameplate amps win. Do not size the wire or breaker from this number: for most motors the NEC sizes the wire, switch and short-circuit protection from its own full-load current tables and the overload from the nameplate amps (NEC 430.6). Switch off and lock out the supply before you open a motor's terminal box: the voltage inside can kill.

Quick answer

A 5 hp three-phase motor on 460 V at 89.5% efficiency and a power factor of 0.82 draws about 6.4 A at full load.

Rule of thumbAmps = hp × 745.7 ÷ (volts × efficiency × power factor), with 1.732 more in the divisor on 3-phase: 5 hp at 460 V, 89.5% and PF 0.82 draws 6.4 A.

NoteEstimates from physics and makers' motor data. Wire, breaker and overload sizes come from the nameplate and the code's motor tables (NEC 430.6): check your code edition and inspector (AHJ). This is an estimate from physics and maker data, not engineering or code advice. Hire a licensed electrician for the work.

Motor full-load amps (FLA) chart by horsepower

A 5 hp three-phase motor draws about 6.4 A on 460 V, 12.8 A on 230 V and 14.1 A on 208 V at its typical figures; the chart runs from 1 to 50 hp.

Estimated full-load amps for three-phase 1,800 rpm motors, from makers' typical efficiency and power factor. An estimate: the code's tables, not this chart, size the wire and breaker; your nameplate wins.
Motor208 V230 V460 V
1 hp3.5 A3.1 A1.6 A
1.5 hp4.8 A4.3 A2.2 A
2 hp6.1 A5.5 A2.7 A
3 hp8.8 A7.9 A4.0 A
5 hp14.1 A12.8 A6.4 A
7.5 hp20.4 A18.4 A9.2 A
10 hp26.6 A24.0 A12.0 A
15 hp39.1 A35.3 A17.7 A
20 hp52.4 A47.4 A23.7 A
25 hp65.8 A59.5 A29.8 A
30 hp79.0 A71.4 A35.7 A
40 hp104.7 A94.7 A47.4 A
50 hp127.3 A115.2 A57.6 A

Single-phase motor amps by horsepower

Estimated single-phase full-load amps at 77% efficiency and a power factor of 0.79, with the low-to-high range in small type, scaled from two makers' 1 hp motors. The range is worked from their efficiency and power factor, so 1 hp tops out at 13.4 A where WEG's nameplate says 13.6 A. A range from maker figures, not a code table; your nameplate wins.
Motor115 V230 V
1 hp10.7 A8.8 to 13.45.3 A4.4 to 6.7
2 hp21.3 A17.6 to 26.910.7 A8.8 to 13.4
3 hp32.0 A26.5 to 40.316.0 A13.2 to 20.1
5 hp53.3 A44.1 to 67.226.6 A22.1 to 33.6

Horsepower (hp) to ampere: the formula

The formula is the one in the quick line above: the efficiency gives the watts the motor takes in, and the power factor (the share of the current that does work) turns them into amps. A DC motor has no power factor. Three-phase volts are measured line to line, and the answer is the current in each line. Skipping both figures with hp × 746 ÷ volts gives 6.5 A for 1 hp at 115 V, where a 1 hp nameplate reads 8.8 A. For a load known in watts, use the watts to amps calculator.

Horsepower to watts and watts to hp

One horsepower is 745.7 W, so watts = hp × 745.7 and hp = watts ÷ 745.7: a 5 hp motor puts out 3,728.5 W at the shaft, and 3 kW is 4.02 hp. Trade sheets often use 746 W, the “electric horsepower”, which is 0.04% higher (NIST). The nameplate hp is shaft power, so the motor takes in more: 4,165.9 W for 5 hp at 89.5%.

Motor efficiency and power factor by size

A 1 hp, 1,800 rpm three-phase motor runs about 85.5% efficient at a power factor near 0.70; by 10 hp it is 91.7% and about 0.85, in Baldor-Reliance, TECO-Westinghouse and WEG catalogs. A flat 0.85 on a 1 hp motor gives 1.3 A on 460 V where its own figures give 1.6 A. Blank boxes use the figures for the size, the nearest smaller size between catalog rows, the 1 hp figures below 1 hp and the 50 hp figures above 50 hp. They suit 1,800 rpm (4-pole) motors; 3,600 rpm motors run a higher power factor. The efficiencies are the NEMA Premium nominal figures the makers print.

Single-phase motor amps on 115 V and 230 V

A 1 hp single-phase motor draws about 8.8 to 13.6 A on 115 V and half that on 230 V, depending on its design: Baldor’s general-purpose motor is rated 8.8 A and WEG’s farm-duty motor 13.6 A. The calculator uses 77% and 0.79, midway between the two, which gives 10.7 A for 1 hp at 115 V, and always shows the range. Dual-voltage 115/230 V motors exist; read the nameplate.

Starting amps: 6 to 10 times the running current

A motor draws about 6 to 10 times its running amps for a moment as it starts: makers’ locked-rotor figures run 6.9 to 10 times for 1 to 3 hp, 6.4 to 7.5 times for 5 to 10 hp and 6.3 to 8.3 times from 15 hp up. Single-phase motors run 6.7 to 8.5 times. Datasheets call it locked-rotor amps. A generator or inverter has to carry that start: see the generator size calculator and the inverter size calculator.

Nameplate amps or the code’s table: which one sizes the wire

For most motors the NEC sizes the wire, switch and short-circuit protection from its own full-load current tables, not from the nameplate or from an estimate like this one, and sets the overload from the nameplate amps (NEC 430.6). IAEI gives the reason: full-load current varies between motors of one size and type, and the tables keep the circuit right when a motor is replaced. Low-speed, high-torque and multispeed motors use the nameplate instead; read the NEC’s motor rules for which. Ask a licensed electrician or your inspector (AHJ) for the circuit. Switch off and lock out the supply before you open a motor’s terminal box: the voltage inside can kill (BITZER, Baldor, WEG).

Part load, 208 V and DC motors: where the estimate drifts

The answer is the current at full rated load and nameplate voltage: an unloaded three-phase motor still draws about 40 to 60 percent of its full-load amps, and a 230 V motor on a 208 V supply draws about 10 percent more. DOE: most motors run at 50 to 100% of rated load, peak near 75%. TECO lists 13.5 A at 208 V for a 5 hp motor rated 12.24 A at 230 V; the chart’s typical figures give 14.1 A and 12.8 A, a little higher because they use a power factor of 0.82, below that model’s 0.855. Both rise about 10% on 208 V. A long run lowers the volts at the motor: the voltage drop calculator shows by how much. DC motors: armature current only; the 83% default comes from 90 V and 180 V motors (Baldor, Leeson), so type the maker’s figure for 12 V or 24 V.

Worked example

  1. Inputs: 5 hp, three-phase, 460 V line to line; typical 5 hp figures 89.5% and 0.82.
  2. Output: 5 hp × 745.7 W = 3,728.5 W
  3. Input: 3,728.5 W ÷ 0.895 = 4,165.9 W
  4. Amps: 4,165.9 W ÷ (1.732 × 460 V × 0.82) = 6.4 A
  5. kVA: 4.17 kW ÷ 0.82 = 5.08 kVA

Questions people ask

How many amps does a 1 hp motor draw?

About 1.6 A on 460 V three-phase and 3.1 A on 230 V, for a 1,800 rpm motor at 85.5% efficiency and a power factor of 0.70. Single-phase 1 hp motors draw more and vary: two makers rate theirs 8.8 A and 13.6 A at 115 V (Baldor, WEG), half that at 230 V. The amps on your nameplate beat any estimate.

Does a motor draw fewer amps on 240 V than on 120 V?

Half as many: a 1 hp motor rated 8.8 A at 115 V is rated 4.4 A at 230 V, for the same power (Baldor's nameplate). Doubling the volts halves the current. A dual-voltage motor has to be connected for the voltage it runs on, at its terminal box, with the power off.

Can I size the wire and breaker from this answer?

No: 6.4 A for a 5 hp motor on 460 V is what the motor draws, and for most motors NEC 430.6 sizes the wire, switch and short-circuit protection from the code's own full-load current tables instead. The overload is set from the motor full load amps on the nameplate. Motors of one size vary, and the tables keep the circuit right for a replacement motor (IAEI). Ask an electrician or your inspector (AHJ).

How many amps does a motor draw when it starts?

About 6 to 10 times its running amps, for a moment as it starts: makers' locked-rotor figures run 6.9 to 10 times for 1 to 3 hp three-phase motors and 6.4 to 7.5 times for 5 to 10 hp. A 5 hp motor drawing 6.4 A on 460 V can pull 40.8 to 47.8 A as it starts.

Why does my clamp meter read less than the calculator?

Because the answer is for full load, and an unloaded three-phase motor still draws about 40 to 60 percent of its full-load amps (Baldor, WEG data), so the current falls much more slowly than the load. Below half load the power factor drops as well (DOE). A reading close to the answer means the motor is working close to its rating.

Related guides

Sources

Data last verified: Page updated

Built and checked by Ali, who is not a licensed electrician.

Before you wire anything

These calculators give estimates worked out from physics and published maker data. They are not engineering, design or code advice, and they do not replace an inspection.

Electrical codes differ by edition and by town. Your local inspector, the authority having jurisdiction (AHJ), has the final say on wire size, conduit, boxes and breakers.

Mains wiring can kill and can start fires. Unless you are trained for it, hire a licensed electrician, and get a permit where your town requires one.