Generator Size Calculator
Running and starting watts for the items you want on, with headroom.
Makers list 150 to 700 W running and 800 to 2,200 W starting.
Makers list 500 to 800 W running and 1,000 to 1,600 W starting.
Makers list 300 to 800 W running and 800 to 2,350 W starting.
Running watts are the steady draw. Starting watts are the extra burst the maker lists; leave it blank for none. If the label gives LRA (locked-rotor amps), LRA × volts is a high estimate.
Up to 12 items.
Your running load will be about 83% of the rating. Generac advises 70 to 85%.
How long will a tank last?
Tanks fill to 80% of their size: a 500 gal tank holds 400 gal (AmeriGas, Ferrellgas).
From your generator's spec sheet at the load nearest your running watts. Fuel use rises with load: Honda lists the EU2200i at 3.2 h on a tank at rated load and 8.1 h at quarter load.
Spec sheets print it as hours on a full tank, e.g. 10 h on 8.5 gal at half load. Type both and the fuel use fills in.
5.8 h
5 gal at 0.85 gal/h runs about 5 h 52 min.
Runtime = fuel on hand ÷ fuel use per hour = 5 gal ÷ 0.85 gal/h = 5.8 h, rounded down
Fuel for 24 hours: 20.4 gal
Natural gas comes through the meter, so there is no tank to run out; this block covers gasoline and propane.
Rated output
No readingRunning watts needed
3,270W
Look for a generator with at least 3,270 W running and 5,070 W starting (peak). Furnace blower 1/2 hp sets the surge (2,350 W).
CheckLast good result. Check the field above.
Propane
Size rangeMost homes use a portable generator of 5,000 to 12,500 W (Champion).
Working
- Running total = 1 × 700 W + 1 × 800 W + 1 × 800 W + 1 × 420 W = 2,720 W
- Highest single start = 2,350 W (Furnace blower 1/2 hp)
- Peak = 2,720 W + 2,350 W = 5,070 W
- Running need = 2,720 W × (1 + 20%) = 2,720 W × 1.20 = 3,264 W, rounded up to 3,270 W
- Load at 120 V = 2,720 W ÷ 120 V = 22.67 A
- Load at 240 V = 2,720 W ÷ 240 V = 11.33 A
Model PL-03
Connect a generator to house wiring only through a transfer switch installed by a licensed electrician; never back-feed an outlet. Estimate from maker data; the lamp stays off because no generator rating is compared. Your generator’s manual wins.
Quick answer
Your items add up to 2,720 W running. Furnace blower 1/2 hp sets the biggest start (2,350 W), so the peak is 5,070 W. With 20% headroom on the running load, look for a generator rated at least 3,270 W running.
Rule of thumbTypical: add the running watts, then the single biggest starting burst: 2,720 W running + 2,350 W start = 5,070 W peak.
NoteEstimate from physics and maker data. Read the labels; your equipment's manual wins. This is an estimate from physics and maker data, not engineering or code advice. Hire a licensed electrician for the work.
| Figure | Fridge | + sump | + furnace, 420 W lights |
|---|---|---|---|
| Running W | 700 | 1,500 | 2,720 |
| Highest start W | 2,200 | 2,200 | 2,350 |
| Peak W | 2,900 | 3,700 | 5,070 |
| Running + 20% W | 840 | 1,800 | 3,270 |
| Peak kW | 2.9 | 3.7 | 5.1 |
Each bundle adds the running watts, then the single highest starting figure once. The typed item has no starting burst.
How the size is worked out
A generator has two ratings. The running (rated) watts are what it can supply all day. The starting (peak) watts last a few seconds, enough to start a motor. Your list needs both, so the calculator makes two sums.
The first sum is the running total: each item’s quantity times its running watts. The second is the peak. Motors draw an extra burst when they start, but rarely in the same instant, so the makers say to add only the single highest starting figure to the running total. Briggs & Stratton, Champion, Generac and the Westinghouse manual all give the same instruction, and the Westinghouse example (2,410 running plus 1,600 starting is 4,010) is one of this page’s test cases.
Add the starting figure as printed, not the difference between starting and running watts. That motor’s running watts are already in the running total, so subtracting first would leave the generator too small.
Headroom and the running need
The running need is the running total plus the headroom you choose. The default is 20%, which puts the running load at about 83% of the generator’s rating, inside the band Generac gives for best performance. The headroom goes on the running watts only; the start is a short burst, so the peak stays as it is.
Every figure that tells you how big to buy is rounded up: watts to the next 10 W, kW to one decimal place. The amps beside them show the running load at 120 V and 240 V.
The three presets and everything else
The item list has three motor presets, because a motor’s start is the number most people cannot read off a label: a refrigerator or freezer, a 1/3 hp sump pump and a 1/2 hp furnace blower. Each sits at the top of the makers’ range, shown in the hint under the row; you can change either number.
Everything else is typed. Heaters, lights, TVs and most electronics print their watts on the label and have no extra start, so type the watts and leave the starting box blank. If a label gives amps, use the amps × volts boxes on a typed item.
There is no preset for central air, a well pump or a microwave: makers’ numbers for them differ by a factor of two or three.
Makers disagree on the start of a 3-ton unit: 5,000 to 6,000 W (Champion) against 15,000 to 18,000 W (Generac). The outdoor unit’s nameplate settles it with the locked-rotor amps (LRA); spec tables list 77 A for one Carrier 3-ton and 83.3 A for one Goodman. Type LRA × volts as the starting watts of a typed item for a high estimate, or ask the installer about a soft start.
Gasoline, propane and natural gas
On propane a generator delivers less than its gasoline rating, so Propane shows the gasoline rating to look for: both needs divided by the propane factor. Natural gas varies more by maker, so use your model’s natural-gas rating.
How long a tank lasts
Open “How long will a tank last?” under the headroom buttons. Runtime is the fuel on hand divided by the fuel use per hour, in the same unit: 4.7 gallons at 1.2 gallons an hour runs 3.9 hours, rounded down.
Take the fuel use from your generator’s spec sheet at the load nearest your running watts, because it rises with load. If the sheet prints hours on a full tank, type both numbers into the helper boxes.
A gallon of propane weighs 4.24 pounds, so a 20 lb cylinder holds about 4.7 gallons. Tanks fill to 80% of their size, so a 500 gallon tank holds 400 gallons. Natural gas comes through the meter, so it has no tank to run out.
Wiring it to the house
A portable generator connects to the house only through a transfer switch installed by a licensed electrician. Never back-feed a circuit through an outlet. The calculator does not size the transfer switch, cords or circuits.
What this estimate is
The result is an estimate from physics and published maker figures, with every step shown. It counts only the items you list. Altitude, heat and a worn engine lower what a generator delivers, and the page does not model them. When the manual or label disagrees, the manual wins.
Worked example
- Inputs: 1 × Refrigerator or freezer: 700 W running, 2,200 W starting; 1 × Sump pump 1/3 hp: 800 W running, 1,600 W starting; 1 × Furnace blower 1/2 hp: 800 W running, 2,350 W starting; 1 × Lights and TV: 420 W running, no starting burst; Headroom on running watts: 20%; Fuel: gasoline.
- Running total = 1 × 700 W + 1 × 800 W + 1 × 800 W + 1 × 420 W = 2,720 W
- Highest single start = 2,350 W (Furnace blower 1/2 hp)
- Peak = 2,720 W + 2,350 W = 5,070 W
- Running need = 2,720 W × (1 + 20%) = 2,720 W × 1.20 = 3,264 W, rounded up to 3,270 W
- Load at 120 V = 2,720 W ÷ 120 V = 22.67 A
- Load at 240 V = 2,720 W ÷ 240 V = 11.33 A
Questions people ask
What size generator do I need?
Add the running watts of everything you want on at once, then add the single biggest starting burst once. Running watts are the steady draw. Starting watts are the extra burst a motor needs for two to three seconds, usually two to three times its running watts (Briggs & Stratton, Generac). Heaters and lights need no extra start. Pick a generator whose running rating covers your running need and whose starting rating covers that total.
How big a generator do I need to run a house?
Size it from the items you list, not from the floor area, because the makers differ. Generac says a 2,000 sq ft home typically needs a 20 kW or 22 kW unit for whole-home coverage. Champion lists 5,000 to 7,500 W for the essentials in a home that size, and 10,000 W or more with central air.
Does propane or natural gas change the size?
Yes. Propane gives about 10% less than gasoline (Champion); a dual-fuel Westinghouse unit is rated 9,500 W on gasoline and 8,500 W on propane. For propane the calculator divides both needs by 0.89. Natural gas runs about 20 to 27% under gasoline on maker sheets (a Westinghouse WGen9500TFc is rated 7,500 against 9,500 W running, a Firman portable unit 5,500 against 7,500 W), so use your model's natural-gas rating.
Can I plug a portable generator into my house?
Not into an outlet. A generator joins house wiring only through a transfer switch installed by a licensed electrician (Champion, Briggs & Stratton), and most jurisdictions require an electrical permit (Generac). Back-feeding an outlet can energize the utility lines and hurt a lineworker.
How long will a 20 lb propane tank run a generator?
A full 20 lb cylinder holds about 4.7 gallons (20 lb ÷ 4.24 lb per gallon). How long it lasts depends on the generator and the load: Champion lists 5 hours at half load for its 9,200 W tri-fuel unit and up to 21 hours at quarter load for its 4,500 W dual-fuel inverter. Divide the tank by your model's fuel use per hour, or open "How long will a tank last?" above.
How much fuel does a generator use per hour?
Read your model's run-time line and divide the tank by the hours. Honda's EU2200i runs 3.2 hours on 0.95 gallon at its 1,800 W rating, about 0.3 gallon an hour, and 8.1 hours at quarter load. A 20 kW Kohler home standby unit burns about 2.2 gallons of propane an hour at half load and 3.7 at full load (82 and 136 cubic feet an hour on its spec sheet).
Related guides
Sources
- Briggs & Stratton: Choosing a Portable Generatorbriggsandstratton.com
- Champion: What Size Generator Do I Need?championpowerequipment.com
- Champion: Generator Wattage Chartchampionpowerequipment.com
- Generac: What Size Generator Do I Need?generac.com
- Westinghouse WGen5300 owner manual (running and starting watts, worked example)westinghouseoutdoorpower.com
- Generac white paper: Basic Sizing for Mobile Generatorsgenerac.com
- Bob Vila: How Big of a Generator Do I Need?bobvila.com
- Kohler 20RESC(L) spec sheet (propane use in cubic feet an hour, 36.39 ft3 per gallon)apelectric.com
- Honda News: EU2200i technical specifications (run time at rated and quarter load)hondanews.com
- Champion 9,200 W tri-fuel generator (run time on gasoline and a 20 lb propane cylinder)championpowerequipment.com
- AmeriGas: Propane tank sizes (80% fill)amerigas.com
- Ferrellgas: Propane generators (500 gallon tank, 400 usable)ferrellgas.com
Written and checked by Ali, who is not a licensed electrician.
Before you wire anything
These calculators give estimates worked out from physics and published maker data. They are not engineering, design or code advice, and they do not replace an inspection.
Electrical codes differ by edition and by town. Your local inspector, the authority having jurisdiction (AHJ), has the final say on wire size, conduit, boxes and breakers.
Mains wiring can kill and can start fires. Unless you are trained for it, hire a licensed electrician, and get a permit where your town requires one.