Inverter Size Calculator
Continuous and surge watts for your loads, and the battery amps they pull.
Inverter size inputs
Running watts are the steady draw. Starting watts are the extra burst the maker lists; leave it blank for none. If the label gives LRA (locked-rotor amps), LRA × volts is a high estimate.
Up to 12 loads.
Rule of thumb: EDECOA adds 25%, Renogy suggests 1.5 times.
Full-load efficiency is lower than the peak figure on the spec sheet.
Rated output
No readingContinuous rating needed
1,513W
Pick an inverter rated at least 1,513 W continuous (25% headroom) with at least 1,810 W surge.
CheckLast good result. Check the field above.
BatteryRating current at 12 V / 24 V / 48 V: 148.3 / 74.2 / 37.1 A
CableCheck the cable's voltage dropAt 148.3 A the cable and fuse must carry this current: use the inverter maker's cable and fuse table.
Working
- Running = 1 × 150 W + 1 × 1,000 W + 1 × 60 W = 1,210 W
- Surge = 1,210 W + 600 W = 1,810 W (largest single start: Motor load)
- Continuous need = 1,210 W × (1 + 25%) = 1,210 W × 1.25 = 1,512.5 W, rounded up to 1,513 W
- DC amps at load = 1,210 W ÷ (12 V × 0.85) = 118.7 A
- DC amps at rating = 1,512.5 W ÷ (12 V × 0.85) = 148.3 A
- DC amps at surge = 1,810 W ÷ (12 V × 0.85) = 177.5 A
Model PL-05
Estimate from physics and maker data. Lamp: green when the unit you type covers both the continuous need and the surge, red when it misses either, off when you type none. Use the maker’s cable and fuse table. Read the labels; your equipment’s manual wins.
Quick answer
Your loads add up to 1,210 W. With 25% headroom the inverter needs at least 1,513 W continuous and 1,810 W surge, and at 12 V the continuous load pulls about 148.3 A from the battery.
Rule of thumbTypical: 1,210 W of loads + 25% = 1,513 W continuous; at 12 V that pulls about 148.3 A from the battery.
NoteEstimate from physics and maker data. Read the labels; your equipment's manual wins. Use the maker's cable and fuse table. This is an estimate from physics and maker data, not engineering or code advice. Hire a licensed electrician for the work.
| Inverter watts | 12 V | 24 V | 48 V |
|---|---|---|---|
| 300 W | 29.5 | 14.8 | 7.4 |
| 600 W | 58.9 | 29.5 | 14.8 |
| 1,000 W | 98.1 | 49.1 | 24.6 |
| 1,500 W | 147.1 | 73.6 | 36.8 |
| 2,000 W | 196.1 | 98.1 | 49.1 |
| 3,000 W | 294.2 | 147.1 | 73.6 |
Amps = watts ÷ (battery volts × efficiency), rounded up. Higher battery voltage means lower current.
How the size is worked out
An inverter has two ratings that matter. The continuous rating is what it can supply all day. The surge (peak) rating is what it can supply for a few seconds, enough to start a motor. List your loads and the calculator makes the same two checks the makers describe.
The running total is every load’s quantity times its running watts. The continuous rating needed is that total plus headroom, rounded up to the next watt. Headroom is a rule of thumb, not a code rule, so you can set it to 0, 25 or 50% or type your own.
The surge needed is the running total plus the single biggest starting figure. Loads rarely start in the same instant, so adding every start would oversize the inverter. If your loads do start together, tick the switch and the calculator adds all the starts instead.
Battery amps
The inverter pulls its power from the battery as direct current. The current is the AC watts divided by the battery volts and the inverter’s efficiency. The calculator shows it three ways: at your load, at the continuous rating and at the surge, each rounded up because the cable and the battery have to carry it. The Battery line on the plate shows the continuous-rating current at 12, 24 and 48 V side by side, and the table below the quick answer shows common sizes.
Doubling the battery voltage halves the current, which is why large inverters are built for 24 or 48 V. The efficiency box defaults to 85% because efficiency at full load is lower than the peak figure on a spec sheet; a higher number would understate the current.
Current rises as the battery voltage sags during discharge, so treat the figure as a minimum. Above 100 A the page tells you to use the inverter maker’s cable and fuse table. It gives no cable or fuse sizes of its own. The link beside it opens the voltage drop calculator with your battery volts and the amps filled in.
Checking a unit
Type a unit’s continuous and surge watts and the pilot lamp compares them with the need. It lights green when the unit covers both, and red when it misses either. Type watts, not VA: a rating in VA is higher than the real watts, and the maker’s datasheet gives both. Continuous ratings also fall in heat; some makers list a lower figure at 40 °C or above, so a unit that only just passes at room temperature may not hold up in a hot space.
Surge duration and wave shape
Many inverters hold their surge rating for about 5 seconds (Battle Born, and the Magnum MS-PAE spec). A motor that takes longer than that to start can trip the inverter even when the surge number looks big enough.
Choose pure sine for motors and sensitive electronics. Modified sine can be cheaper but is a poorer match for them.
What this estimate is
The result is an estimate from physics and published maker figures, with every step shown so you can check it by hand. It does not know your inverter’s low-voltage shutdown, your battery’s limits or your cable length. When the inverter’s manual disagrees with this page, the manual wins.
Worked example
- Inputs: 1 × Motor load: 150 W running, 600 W starting; 1 × Heater: 1,000 W running, no starting burst; 1 × Laptop charger: 60 W running, no starting burst; Headroom: 25%; Battery: 12 V, inverter efficiency 85%; Starts: one at a time.
- Running = 1 × 150 W + 1 × 1,000 W + 1 × 60 W = 1,210 W
- Surge = 1,210 W + 600 W = 1,810 W (largest single start: Motor load)
- Continuous need = 1,210 W × (1 + 25%) = 1,210 W × 1.25 = 1,512.5 W, rounded up to 1,513 W
- DC amps at load = 1,210 W ÷ (12 V × 0.85) = 118.7 A
- DC amps at rating = 1,512.5 W ÷ (12 V × 0.85) = 148.3 A
- DC amps at surge = 1,810 W ÷ (12 V × 0.85) = 177.5 A
Questions people ask
What size inverter do I need?
Add the running watts of everything that runs at the same time, add headroom, and check that the surge rating covers the biggest start (Xantrex, Nova Electric). For headroom, EDECOA adds 25% and Renogy suggests 1.5 times the total wattage; this page starts at 25% and lets you change it.
Do I need to count surge watts?
Yes for motors and compressors such as a refrigerator, a pump or an air conditioner. They can need several times their running watts for a moment. Type the starting watts from the label, or locked-rotor amps times volts for a high estimate. The calculator adds the single biggest start to the running total; tick the switch if several loads can start together.
How many amps will my inverter pull from the battery?
Watts divided by battery volts times efficiency. A 2,000 W load at 12 V and 87% efficiency pulls about 192 A, which matches Battle Born's own spec for a 2,000 W inverter; at 24 V it is about 96 A and at 48 V about 48 A. This page defaults to 85%, because full-load efficiency is lower than the peak figure.
Pure sine or modified sine?
Pure sine runs everything, including motors, microwaves and sensitive electronics. Modified sine suits basic loads, but it may make some equipment run hotter or work badly (Renogy), and some monitors and laser printers need a sine wave (Xantrex).
Does a VA rating equal watts?
No. Use the watts figure. A Victron inverter sold as 1,600 VA is rated 1,300 W continuous at 25 °C, 1,200 W at 40 °C and 800 W at 65 °C. Enter the watts, not the VA, when you check a unit.
What size power station or solar generator do I need?
Treat its rated output as the inverter size and check its surge number the same way. Capacity in watt-hours is a separate question: it decides how long the loads run, not whether the unit can start them.
Related guides
Sources
- Xantrex: Inverter FAQxantrex.com
- Nova Electric: Selecting the proper inverternovaelectric.com
- EDECOA: Inverter sizing guideedecoa.com
- Renogy: 3000W 12V pure sine wave inverterrenogy.com
- Battle Born: 2000W inverterbattlebornbatteries.com
- Bluetti: How long will a 3kWh power station lastbluettipower.com
- Victron community: Difference VA and W on invertervictronenergy.com
- Magnum Energy MS-PAE spec table (reseller copy)nooutage.com
Written and checked by Ali, who is not a licensed electrician.
Before you wire anything
These calculators give estimates worked out from physics and published maker data. They are not engineering, design or code advice, and they do not replace an inspection.
Electrical codes differ by edition and by town. Your local inspector, the authority having jurisdiction (AHJ), has the final say on wire size, conduit, boxes and breakers.
Mains wiring can kill and can start fires. Unless you are trained for it, hire a licensed electrician, and get a permit where your town requires one.