Three-Phase Power Calculator
kW, kVA, kVAR and line amps for a balanced three-phase load.
Between two lines: 208Y/120, 240 V delta, 400Y/230, 480Y/277, 600Y/347.
Typical at full load; a lightly loaded motor runs lower. Nameplate figures win.
Rated output
Balanced loadReal power
17.67kW
17.67 kW of real power, 20.78 kVA apparent and 10.95 kVAR reactive.
Work in a live 208 V, 240 V or 480 V three-phase panel is a licensed electrician's job: turn the power off, lock it out and test it first, because contact can kill and an arc flash burns (OSHA 29 CFR 1910.333; NIOSH).
Working
- kVA = 1.732 × 480 V × 25 A ÷ 1,000 = 20.78 kVA
- kW = 1.732 × 480 V × 25 A × 0.85 ÷ 1,000 = 17.67 kW
- kVAR = 20.78 kVA × √(1 − 0.85²) = 10.95 kVAR
- Per phase: 17.67 kW ÷ 3 = 5.89 kW
Model PL-06
Balanced load, line-to-line volts; nameplate figures win. Sizing a breaker or wire from these amps? A load that runs 3 hours or more is usually counted at 125% (NEC 210.19(A)(1), 210.20(A)).
Quick answer
A 25 A load on a 480 V three-phase circuit at power factor 0.85 is 17.67 kW of real power and 20.78 kVA of apparent power.
Rule of thumbTypical: 10 kW on three phase draws 12.0 A per line at 480 V and power factor 1, or 14.2 A at 0.85; on 208 V, 27.8 A and 32.7 A.
NoteBalanced-load physics; nameplate figures win. Breakers, wire and panel work: check your code edition and your local inspector (AHJ). This is an estimate from physics and maker data, not engineering or code advice. Hire a licensed electrician for the work.
Line and phase values: wye and delta
| Value | Wye (star) | Delta |
|---|---|---|
| Line-to-line voltage | 480 V | 480 V |
| Phase (winding) voltage | 277.1 V | 480 V |
| Line current | 25.0 A | 25.0 A |
| Phase (winding) current | 25.0 A | 14.4 A |
| Power per phase | 5.89 kW | 5.89 kW |
208Y/120, 400Y/230, 480Y/277 and 600Y/347 services are wye; a 240 V three-wire service is usually delta. The totals are the same either way.
Three-phase amps per kW: 208, 240, 400, 480 and 600 V
| Volts | PF 1 | PF 0.9 | PF 0.85 | PF 0.8 |
|---|---|---|---|---|
| 208 V | 2.78 | 3.08 | 3.27 | 3.47 |
| 240 V | 2.41 | 2.67 | 2.83 | 3.01 |
| 400 V | 1.44 | 1.60 | 1.70 | 1.80 |
| 480 V | 1.20 | 1.34 | 1.42 | 1.50 |
| 600 V | 0.96 | 1.07 | 1.13 | 1.20 |
Multiply by your kW: 10 kW at 480 V and power factor 0.85 is 14.2 A.
How to use the three-phase power calculator
Pick what you know (line amps, kW or kVA), pick the line-to-line voltage and type the power factor: the plate shows kW, kVA, kVAR and the amps in each line together. The power factor (PF) is the share of the apparent power that does real work, from 0.10 to 1. Use 1 for heaters and 0.85 for a motor of 10 hp or more at full load (smaller motors run lower), or the number on the nameplate. The page assumes a balanced load, the same current in all three lines. For DC and single-phase circuits use the watts to amps calculator, which also explains where the 1.732 comes from.
Three-phase power formula: kW, kVA and kVAR
Three-phase real power is kW = 1.732 × volts × amps × power factor ÷ 1,000, with the volts measured between two lines and the amps in one line. Leave out the power factor and the same product is the apparent power in kVA. The reactive power in kVAR is kVA × √(1 − PF²). The example, 25 A at 480 V and power factor 0.85, gives 17.67 kW, 20.78 kVA and 10.95 kVAR. The U.S. Department of Energy writes the same real-power formula for motor input power, and 1.732 is √3, the square root of 3.
Three-phase kW to amps and kVA to amps
Amps per line = kW × 1,000 ÷ (1.732 × volts × power factor): 10 kW at 208 V and power factor 0.85 is 11.76 kVA and draws 32.7 A in each line. From kVA the power factor drops out, so 75 kVA at 480 V is 90.2 A. These amps are where breaker and wire sizing starts. The breaker size calculator and the wire size calculator take them from here, and the amps-per-kW table on this page covers the common voltages.
Phase-to-phase voltage: 208Y/120, 480Y/277 and 240 V delta
Phase-to-phase (line-to-line) voltage is the figure between any two hot wires: 208 V on a 208Y/120 V service, 480 V on 480Y/277 V, 240 V on a 240 V delta, 400 V in much of Europe and 600 V in Canada. Line-to-neutral is the figure from one hot wire to the neutral, 120 V on a 208Y/120 V service and 277 V on 480Y/277 V. IEC 60038 lists these pairs. A wye (star) service joins the three windings at a neutral point. A delta joins them in a ring with no neutral, and a high-leg 240 V delta has one leg at about 208 V to neutral. Typing 120, 277 or 347 V into the volts box shows a warning, because the formula needs the line-to-line figure.
The power triangle: why kVA is bigger than kW
kVA² = kW² + kVAR², so kVA is bigger than kW whenever the power factor is below 1: ABB’s table puts 75 kW at power factor 0.85 at 88.2 kVA and 46.5 kVAR, drawing 106 A at 480 V. Power factor is kW ÷ kVA, the cosine of the PF angle, which is 31.8° in the example. kVAR is the reactive power that builds the magnetizing flux in motors and transformers; it does no work, but the wires still carry it. Generators, UPS units and transformers are rated in kVA: see the generator size calculator and the inverter size calculator.
Single phase vs three phase for the same load
Three phase carries the same power with 1.732 times less current in each wire: 17.67 kW at 480 V and power factor 0.85 draws 25.0 A per line on three phase and 43.3 A on single phase, 42% less. The single-phase figure uses the same voltage and power factor, so the two circuits are compared at one voltage. Wire size is a separate sum for each circuit.
Unbalanced loads and live panels: where the three-phase math stops
Every figure here assumes a balanced load, the same current in all three lines; when the lines differ, check each phase and the neutral on its own, as ABB advises. The Department of Energy averages three readings instead, as the last question below shows. For a motor the nameplate amps win over any calculated figure, and a long run needs the voltage drop calculator. Work in a live panel is a licensed electrician’s job: turn the power off, lock it out and test it first, because contact can kill and an arc flash burns (OSHA 29 CFR 1910.333; NIOSH).
Worked example
- Inputs: 25 A in each line, 480 V line to line, power factor 0.85.
- kVA = 1.732 × 480 V × 25 A ÷ 1,000 = 20.78 kVA
- kW = 1.732 × 480 V × 25 A × 0.85 ÷ 1,000 = 17.67 kW
- kVAR = 20.78 kVA × √(1 − 0.85²) = 10.95 kVAR
- Per phase: 17.67 kW ÷ 3 = 5.89 kW
Questions people ask
How do I calculate three-phase power?
kW = 1.732 × line-to-line volts × line amps × power factor ÷ 1,000, so 25 A at 480 V and power factor 0.85 is 17.67 kW, or 20.78 kVA without the power factor. Use the voltage between two lines, never the 277 V from a line to neutral; the U.S. Department of Energy writes the same formula for motor input power.
How many amps per phase is 75 kVA at 480 V?
90.2 A in each of the three lines: 75,000 ÷ (1.732 × 480). Starting from kVA you need no power factor. Inside a delta winding the current is 1.732 times smaller, 52.1 A.
What is the difference between line current and phase current?
In a delta, a 40 A line current is 23.1 A in each winding, because the line current is 1.732 times the winding current. In a wye (star) the two are the same. The calculator's amps are always line amps, the current in each supply wire.
What happens if I use 277 V instead of 480 V?
The answer comes out 1.732 times too small: 25 A at 277 V in the three-phase formula gives 11.99 kVA, against 20.78 kVA at 480 V. 277 V is the line-to-neutral side of a 480Y/277 V system; the formula needs the 480 V between lines.
How do I get kW from three amp readings?
Average each reading first. The Department of Energy's motor example takes volts of 467, 473 and 469 (average 469.7 V), amps of 36, 38 and 37 (average 37 A) and a power factor of 0.763, then 1.732 × 469.7 × 37 × 0.763 ÷ 1,000 = 22.97 kW (DOE prints 22.9).
Sources
- U.S. DOE: Determining Electric Motor Load and Efficiency (Equation 1)energy.gov
- TAMU ECEN460 Lecture 3: balanced three-phase systemstamu.edu
- MTU EET2233 Chapter 2: balanced three-phase systemsmtu.edu
- ABB Technical Note 174: Introduction to power factorabb.com
- Rex Power Magnetics: How is transformer kVA calculatedrexpowermagnetics.com
- IEC 60038:2009 Standard voltages (public copy)resource.org
- Engineering ToolBox: Electrical distribution systemsengineeringtoolbox.com
- ABB: How to size a transformerabb.com
- 29 CFR 1910.333 (eCFR)ecfr.gov
- NIOSH 2009-113: Electrical safety for the electrical tradescdc.gov
- Square D instruction bulletin 43006-850-01se.com
- Eaton application note AP01200008E: 100%-rated molded case circuit breakerseaton.com
Built and checked by Ali, who is not a licensed electrician.
Link to this calculator: https://wattplate.com/three-phase-power-calculator/
Before you wire anything
These calculators give estimates worked out from physics and published maker data. They are not engineering, design or code advice, and they do not replace an inspection.
Electrical codes differ by edition and by town. Your local inspector, the authority having jurisdiction (AHJ), has the final say on wire size, conduit, boxes and breakers.
Mains wiring can kill and can start fires. Unless you are trained for it, hire a licensed electrician, and get a permit where your town requires one.